JOHNSON CONTROLS
44
FORM 100.50-SU8
ISSUE DATE: 1/28/2016
SECTION 12 - BACNET MS/TP POINTS
TABLE 1 - BACNET MS/TP POINTS (CONT'D)
BACNET NAME
USER
INTERFACE
NAME
READ/
WRITE
BACNET/
OBJECT TYPE
AND INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
SAT_LOW_LIM
SUPPLY AIR
TEMP LO SP
R/W AV27 1052
DISPLAYS THE LOWER LIMIT
FOR THE SUPPLY AIR TEMP SP
ON A VAV UNIT (°F)
SAT_RST_BAS
SUPPLY AIR
TEMP RESET
BAS
R/W AV28 1053
DISPLAYS THE ANALOG INPUT
FROM THE BAS SYSTEM THAT
ALLOWS THE RESET OF THE
ACTIVE SUPPLY AIR TEMP SP.
0 USES SAT HIGH SP AND 5
USES SAT LOW SP. "SAT RST
BAS" MUST BE ENABLED IN
THE SERVICE MENU FOR THIS
POINT TO FUNCTION
SAT_SUC_TMP1
SATURATED
SUCT TEMP
CKT 1
R AI43 556
DISPLAYS THE SATURATION
TEMP OF SYSTEM 1 SUCTION
GAS BASED ON SYSTEM 1
SUCTION PRESS (°F)
SAT_SUC_TMP2
SATURATED
SUCT TEMP
CKT 2
R AI44 557
DISPLAYS THE SATURATION
TEMP OF SYSTEM 2 SUCTION
GAS BASED ON SYSTEM 2
SUCTION PRESS (°F)
SAT_SUC_TMP3
SATURATED
SUCT TEMP CKT
3 (70-150 TON
ONLY)
R AI45 558
DISPLAYS THE SATURATION
TEMP OF SYSTEM 3 SUCTION
GAS BASED ON SYSTEM 3
SUCTION PRESS (°F)
SAT_TEMPER
SUPPLY AIR
TEMPERING
STATUS
R BI53 1334
DISPLAYS THE STATUS OF
SUPPLY AIR TEMPERING:
ON/OFF
SEN/MSC_FLT
SENSOR/MISC
FAULT STATUS
R BI54 1335
DISPLAYS THE STATUS OF A
SENSOR OR MISC FAULT:
0=NO FAULT 1=FAULTED
SF_PROV_SW
SUPPLY FAN
STATUS
R BI55 1336
DISPLAYS THE STATUS
OF THE SUPPLY FAN AIR
PROVING CIRCUIT: 0=STOP
VERIFICATION/CKT OPEN
1=RUN VERIFICATION/CKT
CLOSED
SF_SPD_H_SAT
FAN SPEED SP
FOR HI SUPPLY
AIR TEMP
R/W AV29 1054
DISPLAYS THE SUPPLY
FAN SPEED SP USED FOR
SWITCHING TO THE HIGH
SUPPLY AIR TEMP SP
SF_SPD_L_SAT
FAN SPEED SP
FOR LO SUPPLY
AIR TEMP
R/W AV30 1055
DISPLAYS THE SUPPLY
FAN SPEED SP USED FOR
SWITCHING TO THE LOW
SUPPLY AIR TEMP SP
SMOKE_PUR_1
SMOKE PURGE
1 STATUS
R BI56 1337
DISPLAYS THE STATUS OF
THE SMOKE PURGE 1 INPUT
EITHER HARDWIRED OR
COMMUNICATED: ON/OFF