SECTION 12 - BACNET MS/TP POINTS
FORM 100.50-SU8
ISSUE DATE:1/28/2016
12
TABLE 1 - BACNET MS/TP POINTS (CONT'D)
BACNET NAME
USER
INTERFACE
NAME
READ/
WRITE
BACNET/
OBJECT TYPE
AND INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
SMOKE_PUR_2
SMOKE PURGE
2 STATUS
R BI57 1338
DISPLAYS THE STATUS OF
THE SMOKE PURGE 2 INPUT
EITHER HARDWIRED OR
COMMUNICATED: ON/OFF
SMOKE_PUR_3
SMOKE PURGE
3 STATUS
R BI58 1339
DISPLAYS THE STATUS OF
THE SMOKE PURGE 3 INPUT
EITHER HARDWIRED OR
COMMUNICATED: ON/OFF
SMOKE_PUR1_B
SMOKE PURGE
1 BAS
R/W AV90 BV14 1115
A BAS COMMAND THAT ALLOWS
SMOKE PURGE 1 TO BE
ACTIVATED: 0=OFF 1=ON
SMOKE_PUR2_B
SMOKE PURGE
2 BAS
R/W AV91 BV15 1116
A BAS COMMAND THAT
ALLOWS SMOKE PURGE 2 TO
BE ACTIVATED: 0=OFF 1=ON
SMOKE_PUR3_B
SMOKE PURGE
3 BAS
R/W AV92 BV16 1117
A BAS COMMAND THAT ALLOWS
SMOKE PURGE 3 TO BE
ACTIVATED: 0=OFF 1=ON
STG_1_COOL
1ST STAGE
COOLING SP
(CV AND SZVAV
ONLY)
R/W AV31 1056
DISPLAYS THE ACTIVE SUPPLY
AIR TEMP SP FOR A 1ST STAGE
COOLING INPUT (Y1)
STG_1_HEAT
1ST STAGE
HEATING SP
(CV AND SZVAV
ONLY)
R/W AV32 1057
DISPLAYS THE ACTIVE SUPPLY
AIR TEMP SP FOR A 1ST STAGE
HEATING INPUT (W1)
STG_2_COOL
2ND STAGE
COOLING SP
(CV AND SZVAV
ONLY)
R/W AV33 1058
DISPLAYS THE ACTIVE SUPPLY
AIR TEMP SP FOR A 2ND STAGE
COOLING INPUT (Y2)
STG_2_HEAT
2ND STAGE
HEATING SP
(CV AND SZVAV
ONLY)
R/W AV34 1059
DISPLAYS THE ACTIVE SUPPLY
AIR TEMP SP FOR A 2ND STAGE
HEATING INPUT (W2)
SUP_AIR_TEMP
SUPPLY AIR
TEMP CURRENT
R AI46 559
CV or VAV: DISPLAYS THE
ACTUAL TEMP OF THE SUPPLY
AIR (°F)
FLEXSYS: DISPLAYS THE
ACTUAL TEMP OF THE MX
SUPPLY AIR TEMP (°F)
SUP_AIR_TRST
SUPPLY AIR
TEMP RESET
R AI47 560
DISPLAYS THE VALUE, 0-5
VDC, OF A HARDWIRED OR
COMMUNICATED INPUT THAT
WILL BE USED TO RESET THE
SUPPLY AIR TEMP SP (VDC)
SUP_FAN_VFD
SUPPLY FAN
VFD SPEED
R AI48 561
DISPLAYS THE OUTPUT FROM
THE CONTROL TO THE SUPPLY
FAN VFD (%)