JOHNSON CONTROLS
46
FORM 100.50-SU8
ISSUE DATE: 1/28/2016
SECTION 12 - BACNET MS/TP POINTS
TABLE 1 - BACNET MS/TP POINTS (CONT'D)
BACNET NAME
USER
INTERFACE
NAME
READ/
WRITE
BACNET/
OBJECT TYPE
AND INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
SUPPLY_FAN
SUPPLY FAN
OUTPUT STATUS
R BI59 1340
DISPLAYS THE STATUS OF
THE OUTPUT FROM THE
CONTROLLER TO THE SUPPLY
FAN CIRCUIT: 0=OFF 1=ON
SYSTEM_STOP SYSTEM STOP R/W AV35 1060
ALLOWS A BAS COMMAND
THAT MANUALLY SHUTS
DOWN COMPRESSOR
CIRCUITS: 0=ALL CKTS CAN
OPERATE 1=SHUTS DOWN
CKT 1 2=SHUTS DOWN CKT 2
3=SHUTS DOWN CKT 3
SZ_MIN_VFD
SINGLE ZONE
VAV MIN FAN
SPEED
R/W AV53 NA*
THIS IS THE MINIMUM SPEED
THE SUPPLY FAN VFD WILL
OPERATE AT WHEN IN SINGLE
ZONE VAV MODE
TEMP_1_SUCT
SUCT TEMP
CKT 1
R AI49 562
DISPLAYS THE ACTUAL SYSTEM
1 SUCT LINE TEMP (°F)
TEMP_1_SUPER
SUCT
SUPERHEAT
CKT 1
R AI50 563
DISPLAYS THE SYSTEM 1
SUPERHEAT (°F)
TEMP_2_SUCT
SUCT TEMP
CKT 2
R AI51 564
DISPLAYS THE ACTUAL SYSTEM
2 SUCT LINE TEMP (°F)
TEMP_2_SUPER
SUCT
SUPERHEAT
CKT 2
R AI52 565
DISPLAYS THE SYSTEM 2
SUPERHEAT (°F)
TEMP_3_SUCT
SUCT TEMP
CKT 3 (70-150
TON ONLY)
R AI53 566
DISPLAYS THE ACTUAL SYSTEM
3 SUCT LINE TEMP (°F)
TEMP_3_SUPER
SUCT
SUPERHEAT
CKT 3 (70-150
TON ONLY)
R AI54 567
DISPLAYS THE SYSTEM 3
SUPERHEAT (°F)
UND_FLR_DEWP
UNDERFLOOR
SLAB DEW
POINT
(FLEXSYS)
R AI55 568
DISPLAYS THE CALCULATED
DEW POINT OF THE
UNDERFLOOR AIR (°F)
UND_FLR_HUMD
UNDERFLOOR
AIR HUMIDITY
(FLEXSYS)
R AI56 569
DISPLAYS THE HUMIDITY VALUE
OF THE UNDERFLOOR AIR (°F)
UND_FLR_TEMP
UNDEFLOOR
SLAB TEMP
(FLEXSYS)
R AI57 570
DISPLAYS THE TEMP OF THE
UNDERFLOOR SLAB (°F)
UND_HUMD_BAS
UNDERFLOOR
AIR HUMIDITY
BAS (FLEXSYS)
R/W AV36 1061
ALLOWS THE BAS SYSTEM
TO INPUT AN UNDERFLOOR
AIR HUMIDITY VALUE TO THE
CONTROL. (% RH) "UNDER FLR
HUMI BAS" MUST BE ENABLED
IN THE SERVICE MENU FOR
THIS POINT TO FUNCTION