FX-PCG16 General Purpose Programmable Controller
Installation Instructions
FX-PCG1611-x, FX-PCG1621-x
Part No. 24-10143-152, Rev. G
Issued April 2016
Refer to the QuickLIT website for the most up-to-date version of this document.
Application
The FX-PCG16 controller is part of the Facility Explorer
Controller FX-PCG family. The FX-PCG16 controller runs
pre-engineered and user-programmed applications and
provides the inputs and outputs required to monitor and
control a wide variety of HVAC equipment.
The FX-PCG controllers operate on an RS-485 BACnet®
Master-Slave/Token-Passing (MS/TP) Bus as BACnet
Application Specific Controllers (B-ASC) and integrate
into Johnson Controls® and third-party BACnet systems.
With Release 10.1, you can use the FX-PCT software
to switch the FX-PCG to use the N2 protocol.
The FX-PCG16 controller is available with or without an
integral LCD and push button user interface.
Switchable Communications
Protocols
By default, the FX-PC family controllers and network
sensors communicate using the standard BACnet
protocol, based on the ANSI/ASHRAE 135-2004.
The BACnet protocol is a standard for ANSI, ASHRAE,
and the International Standards Organization (ISO) for
building controls.
FX-PCG, FX-PCX, and FX-PCV controllers are BTL-
tested and listed as BACnet Application Specific
Controllers (B-ASCs). FX-PCA field controllers are
BTL-listed as BACnet Advanced Application Controllers
(B-AACs). The NS Series Sensors are BTL-listed as
BACnet Smart Sensors (B-SSs).
Release 10.1 of FX-PCT and later can be used to switch
the Field Bus communications protocol in FX-PC
Controllers to be either the standard BACnet
Master-Slave/Token-Passing (MS/TP) or the N2 protocol.
BACnet MS/TP is the default communications protocol
for all new controllers. Switchable communications
protocols provide a cost-effective upgrade and
modernization path for customers with existing N2
controllers. The Modernization Guide for Legacy N2
Controllers (LIT-12012045) and the controller-specific
documentation provide installation and commissioning
support and include tips for efficient and safe
replacement. Refer to the N2 Compatibility Options
chapter of the Controller Tool Help (LIT-12011147) for
information about mapping N2 Objects in controllers with
switchable communications protocols.
The N2-capable FX-PC controllers can be used as
functional replacements for legacy N2 controllers. The
N2-capable FX-PC controllers:
have the I/O quantities and characteristics of the
FX-PC family controllers
must be programmed with FX-PCT, which has
programming capabilities that are similar (but not
identical) to HVACPro, GX9100, GPL, and other
legacy tools
support SA Bus devices
support FX-WRZ wireless sensors from the controller
using the FX-WRZ7860 receiver when configured for
BACnet MS/TP communication
The N2-capable FX-PC controllers:
do not support Zone Bus (for example, TMZ sensors
and M100 actuators)
do not support pass through in the commissioning
mode
do not support remote downloading or commissioning
using BACnet routing
do not support wireless connection to the N2 bus
1FX-PCG16 General Purpose Programmable Controller Installation Instructions

Questions and Answers:

Johnson Controls FX-PCG1621 Series Specifications

General IconGeneral
ModelFX-PCG1621 Series
TypeProgrammable Controller
Input Points16
Output Points21
Communication ProtocolBACnet/IP, BACnet MS/TP
Power Supply24 VAC/VDC
MountingDIN rail
Humidity Range10% to 90% non-condensing
Enclosure RatingIP20
Memory512 KB

Summary

Installation

Mounting

General guidelines for properly mounting the FX-PCG controller.

DIN Rail and Wall Mounting

DIN Rail Mounting

Step-by-step instructions for mounting the controller on a 35 mm DIN rail.

Wall Mounting

Instructions for mounting the controller directly onto a wall or flat vertical surface.

Terminal Wiring Guidelines

General Wiring Precautions

Covers safety, electrical ratings, and electrostatic discharge precautions.

Terminal Block and Bus Port Overview

Identifies and describes terminal blocks and bus ports on the controller.

Supply Power Terminal Block Wiring

Instructions for wiring the 24 VAC supply power terminal block.

Wireless Network Configuration

Steps to configure the controller for use with the FX-ZFR1811 Wireless Field Bus.

Termination Diagrams

Input and Output Wiring Guidelines

Terminal Block Functions

Details functions, ratings, and requirements for FX-PCG terminal blocks.

SA/FC Bus and Supply Power Wiring Guidelines

Bus and Power Terminal Block Details

Details functions, ratings, and cable types for bus and power terminals.

Setup and Adjustments

Setting Device Addresses

How to set unique device addresses for controllers on MS/TP buses.

Device Address Table

Lists valid device addresses for MS/TP controllers.

Commissioning and Troubleshooting

Controller Commissioning Process

Overview of commissioning controllers using FX-PCT software.

Troubleshooting with Status LEDs

How to use status LEDs to diagnose controller issues.