FX-PCV1615/1626/1628/1630 Programmable
VAV Box Controllers Installation
Instructions
Applications
The FX-PCV1615/1626/1628/1630 programmable digital controllers are designed for controlling
Variable Air Volume (VAV) boxes. These FX-PCV Variable Air Volume Modular Assembly (VMA)
controllers feature combinations of an integral digital pressure sensor (DPT), a damper actuator,
and a 32-bit microprocessor. The FX-PCV1626 has an actuator but does not contain a DPT. The FX-
PCV1628 model has a DPT but does not contain an actuator. The controllers' small package size
facilitates quick field installation and efficient use of space without compromising high-tech control
performance. These FX-PCV controllers connect easily to the wired and wireless network sensors for
zone and discharge air temperature sensing.
Communications protocol
The FX-PC family controllers and network sensors communicate using the standard BACnet
®
protocol, based on the ANSI/ASHRAE 135-2008. The BACnet protocol is a standard for ANSI,
ASHRAE, and the International Standards Organization (ISO) for building controls.
FX-PCV controllers are BTL-listed as BACnet Application Specific Controllers (B-ASCs).
The Controller Configuration Tool (CCT) can be used to switch the Field Bus communications
protocol in supported FX-PC Controllers to be either the standard BACnet MS/TP or the N2 protocol.
All new controllers use either BACnet MS/TP as the default communications protocol, or BACnet/
IP. Switchable communications protocols in the MS/TP models provide a cost-effective upgrade and
modernization path for customers with existing N2 controllers.
The Modernization Guide for Legacy N2 Controllers (LIT-12012045) and the controller-specific
documentation provide installation and commissioning support and include tips for efficient
and safe replacement. Refer to the N2 Compatibility Options chapter of the Controller Tool
Help (LIT-12011147) for information about mapping N2 Objects in controllers with switchable
communications protocols.
The N2-capable FX-PC Controllers can be used as functional replacements for legacy N2 controllers.
The N2-capable FX-PC Controllers:
have the I/O quantities and characteristics of the FX-PC family controllers
must be programmed with CCT, which has programming capabilities that are similar (but not
identical) to HVACPro, GX9100, GPL, and other legacy tools
support SA Bus devices
support FX-WRZ wireless sensors from the controller using the FX-WRZ7860 receiver when
configured for BACnet MS/TP communication
The N2-capable FX-PC controllers:
do not support Zone Bus (for example, TMZ sensors and M100 actuators)
do not support passthrough in the commissioning mode
do not support remote downloading or commissioning using BACnet routing
do not support wireless connection to the N2 bus
Part No. 24-10143-357 Rev. H
2019-03-22
(barcode for factory use only)
FX-PCV1615, FX-PCV1626, FX-PCV1628, FX-PCV1630
*2410143357H*

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls FX-PCV1630 and is the answer not in the manual?

Johnson Controls FX-PCV1630 Specifications

General IconGeneral
BrandJohnson Controls
ModelFX-PCV1630
CategoryController
LanguageEnglish

Related product manuals