EasyManua.ls Logo

Johnson Controls Metasys NCE25 series - Communications Bus and Supply Terminal Blocks

Johnson Controls Metasys NCE25 series
38 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 13: Cable length guidelines for recommended wire sizes
Guideline Wire size/gauge and type Maximum cable
length and type
Assumptions
C See Figure 13 to select wire size/
gauge. Use stranded copper wire.
See Figure 13 to
determine cable
length. Use twisted
wire cable.
N/A
Maximum cable length versus load current
In most cases inputs/outputs with cables less than 30 m (100 ft) do not require an offset in the
software setup. Cable runs over 30 m (100 ft) may require an offset in the input/output software
setup.
Use Figure 13 to estimate the maximum cable length relative to the wire size and the load current
(in mA) when wiring inputs and outputs.
Figure 13: Maximum wire length by current and wire size
Communications Bus and supply terminal blocks, functions,
ratings, requirements, and cables
Table 14: Communications bus and supply terminal blocks, functions, ratings, requirements, and
cables
Terminal
block/port
label
Terminal
labels
Function, electrical ratings/requirements Recommended cable
type
+
_
FC Bus Communications
COM Signal Reference (Common) for bus
communications
FC BUS
SHLD Isolated terminal (optional shield drain
connection)
0.6 mm (22 AWG)
stranded, 3-wire
twisted, shielded cable
recommended
NCE25 Installation Instructions26

Related product manuals