Table 29: 4 ton cooling charging chart for XAF*60H and
JH(E,V)T*60H in upflow
Indoor wet bulb (°F) at 80°F dry bulb
57 62 67 72
Outdoor
ambient
DB (°F)
Pressure (psig) and subcooling
(°F) at liquid base valve
55 210 (7) 213 (7) 216 (7) 221 (8)
60 227 (6) 230 (7) 233 (7) 238 (7)
65 244 (6) 247 (7) 250 (7) 254 (7)
70 264 (6) 267 (7) 270 (7) 274 (7)
75 284 (7) 287 (7) 290 (7) 293 (7)
80 307 (7) 309 (8) 312 (8) 316 (8)
85 329 (8) 331 (8) 334 (8) 338 (8)
90 355 (8) 357 (9) 359 (9) 363 (8)
95 380 (9) 382 (9) 384 (9) 388 (8)
100 408 (9) 409 (9) 412 (9) 415 (8)
105 436 (9) 437 (9) 440 (9) 443 (8)
110 467 (8) 468 (9) 470 (8) 474 (8)
115 498 (8) 498 (9) 501 (8) 504 (7)
120 531 (8) 531 (9) 534 (8) 537 (7)
125 564 (8) 564 (9) 567 (8) 570 (7)
Table 30: 4 ton cooling charging chart for XAH*60H and
JH(E,V)T*60H in horizontal left
Indoor wet bulb (°F) at 80°F dry bulb
57 62 67 72
Outdoor
ambient
DB (°F)
Pressure (psig) and subcooling
(°F) at liquid base valve
55 213 (8) 216 (8) 220 (8) 225 (9)
60 231 (7) 234 (8) 237 (8) 242 (8)
65 248 (7) 251 (8) 254 (8) 258 (8)
70 269 (7) 271 (8) 274 (8) 278 (8)
75 289 (8) 291 (8) 294 (8) 298 (8)
80 312 (8) 314 (9) 317 (9) 321 (9)
85 335 (9) 337 (9) 340 (9) 343 (9)
90 360 (9) 362 (10) 365 (10) 369 (9)
95 386 (10) 388 (10) 390 (10) 394 (9)
100 415 (10) 416 (10) 419 (10) 422 (9)
105 443 (10) 444 (10) 447 (10) 450 (9)
110 474 (9) 475 (10) 478 (9) 481 (9)
115 505 (9) 506 (10) 509 (9) 512 (8)
120 539 (9) 539 (10) 542 (9) 546 (8)
125 573 (9) 573 (10) 576 (9) 579 (8)
Table 31: 4 ton cooling charging chart for XA(F,H)*60H
and JH(E,V)T*60H in downflow and horizontal right
Indoor wet bulb (°F) at 80°F dry bulb
57 62 67 72
Outdoor
ambient
DB (°F)
Pressure (psig) and subcooling
(°F) at liquid base valve
55 218 (9) 221 (10) 224 (10) 229 (11)
60 235 (9) 238 (10) 242 (10) 246 (10)
65 253 (9) 256 (9) 259 (10) 263 (10)
70 274 (9) 277 (10) 280 (10) 284 (10)
75 294 (9) 297 (10) 300 (10) 304 (10)
80 318 (10) 320 (11) 323 (11) 327 (11)
85 341 (11) 343 (12) 346 (11) 350 (11)
90 367 (11) 369 (12) 372 (12) 376 (12)
95 394 (12) 395 (13) 398 (12) 402 (12)
100 423 (12) 424 (13) 427 (12) 430 (12)
105 452 (12) 453 (13) 456 (12) 459 (11)
110 484 (11) 484 (12) 487 (12) 490 (11)
115 515 (11) 516 (12) 519 (11) 522 (10)
120 550 (11) 550 (12) 553 (11) 556 (10)
125 585 (11) 584 (12) 587 (11) 591 (10)
Table 32: 5 ton cooling charging chart for
XA(F,H)*60(H,J) and JH(E,V)T*60(H,J) in upflow,
downflow, and horizontal right
Indoor wet bulb (°F) at 80°F dry bulb
57 62 67 72
Outdoor
ambient
DB (°F)
Pressure (psig) and subcooling
(°F) at liquid base valve
55 193 (9) 198 (10) 197 (10) 197 (10)
60 211 (9) 215 (10) 215 (10) 215 (10)
65 229 (9) 233 (9) 233 (10) 234 (10)
70 246 (9) 250 (9) 251 (10) 253 (10)
75 264 (9) 268 (9) 270 (9) 272 (10)
80 287 (9) 290 (9) 292 (9) 294 (10)
85 310 (9) 312 (9) 314 (9) 317 (10)
90 333 (9) 334 (9) 336 (9) 339 (10)
95 357 (9) 356 (9) 358 (9) 361 (10)
100 385 (9) 384 (9) 386 (9) 390 (10)
105 413 (9) 413 (9) 415 (9) 419 (10)
110 441 (9) 441 (9) 443 (9) 447 (10)
115 469 (9) 470 (9) 472 (9) 476 (10)
120 497 (9) 498 (9) 501 (9) 505 (10)
125 525 (9) 527 (9) 530 (9) 534 (9)
Installation Manual: R-410A Outdoor Split-System Heat Pump - YH2F, THF2, RHP150 Series22