T600HCx-3 Single-Stage Thermostats Installation Instructions6
Lockout Selectable Lockout Levels for
limiting end-user keypad interaction.
Default: 0
Function Lockout Level
(0) (1) (2)
Occupancy
Override
Access Access No Access
Permanent
Temperature
Setpoints
Access No Access No Access
Temporary
Temperature
Setpoints
Access Access No Access
System Mode
Setting
Access No Access No Access
Fan Mode Setting Access No Access No Access
Schedules
Setting
2
Access No Access No Access
Clock Setting
2
Access Access Access
Permanent Hold
2
Access No Access No Access
Pwr del
3
Sets the delay time period at
thermostat power up, or at each
time power is removed and
reapplied, before any operation
(fan, heating, or cooling) is
authorized. Also can be used to
sequence the startup of multiple
units in one location.
Default: 10.0 sec
Range: 10.0 to 120.0 sec
Frost pr Provides a minimum heating
setpoint of 42.0°F/5.5°C to prevent
freezing in the zone controlled by
the thermostat.
Default: off
(on): Enabled
(off): Disabled
Heat max
4
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
Range: 40.0°F/4.5°C to 90.0°F/32.0°C
Cool min
4
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 54.0°F/12.2°C
Range: 54.0°F/12.2°C to 100.0°F/37.7°C
Anticycl Anti-Short Cycle timer sets the
minimum on/off times for heating
and cooling.
Default: 2.0 min
Range: 0.0 to 5.0 min adjustable in 1-minute increments
Set the anti-short cycle timer to 0.0 min for equipment that already
has its own anti-short cycle timer.
Heat cph Sets the maximum number of
Heating cycles per hour.
Default: 4.0
Range: 3.0 to 8.0 cycles per hour
Cool cph Sets the maximum number of
Cooling cycles per hour.
Default: 4.0
Range: 3.0 or 4.0 cycles per hour
Table 2: Installer Configuration Menu (Part 2 of 4)
Parameter
Appearing
on Display
Description and Default Selection Options