T600HCx-3 Single-Stage Thermostats Installation Instructions 7
Deadband Sets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°
Range: 2.0F°/1.0C° to 4.0F°/2.0C° adjustable in 1.0F°/0.5C°
increments
Fan cont Determines how the fan is activated
in response to a call for heating.
Fan cont applies to W1 and Fan
Mode auto only. Fan cont does not
affect fan operation on a call for
cooling (Y1).
Default: on
(off): The thermostat does not activate the fan in response to a call
for heating. The fan is activated by the equipment fan and limit
control.
(on): Enables the thermostat to activate the fan in response to a call
for heating or cooling.
Fan del Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default off
(on): Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off): No extension of fan operation after a heating or cooling cycle
has ended.
The fan delay is only active when the fan is in the Auto mode.
TOccTime Sets the duration of the Temporary
Occupancy Time (when the
thermostat is in the Unoccupied
mode) when a Schedule Override
Function is enabled using either the
Main User Menu or DI1 or DI2
configured as a temporary override
remote contact (RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the up/down
arrow keys.
default: 3.0 hrs
Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
Cal RS Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°C
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
increments
Cal OS Sets the desired outdoor air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°
Range: -5.0F°/-2.5C° to 5.0F°2.5C° adjustable in 1.0F°/0.5C°
increments
H lock Discontinues heating operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: 120°F/49°C
Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C° increments
C lock Discontinues cooling operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: -40°F/-40°C
Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
Table 2: Installer Configuration Menu (Part 3 of 4)
Parameter
Appearing
on Display
Description and Default Selection Options