FAN-8941(1123)
Parameter
Item
Parameter Name
Parameter Setting
Range
(Default Value)
Functional Meaning Applicable Model
P2
Dry contact input function
selection
00
00: Key card function (open)
All
01: Key card function (closed)
02: External sensor
03: Dew point risk warning (open)
04: Dew point risk warning (closed)
05: The open circuit indicates that the room is occupied, while
the short circuit indicates that the room is unoccupied, and the
fans and valves are shut off.
P3
Temperature display on
the LCD screen
00
00: The room temperature is displayed when it is in the normal state. All
01: The set temperature is displayed when it is in the normal state.
P4
Conversion between
Celsius and Fahrenheit
00 00: Celsius (℃ ); 01: Fahrenheit (°F) All
P5 Product model definition /
00: NG1; 01: NG2; 02: NG3: 03: NG4; 04: NG5
Users cannot modify them, and only product models are
displayed.
All
P6 Application selection 00
T7300-TF60-9KS0:
00: Support 2-pipe on-off 2/3-wire valves, 3-speed fans and
the TiO2/ESP function
01: Support 4-pipe on-off 2/3-wire valves and 3-speed fans
T7700-TF60-9KS0:
00: Support 2-pipe on-off 2/3-wire valves, 3-speed fans,
Modbus RTU communication and the TiO
2
/ESP function
01: Support 4-pipe on-off 2/3-wire valves, 3-speed fans and
Modbus RTU communication
T7300-TF60-9MS0:
00: Support 2-pipe on-off 2/3-wire valves, ECM fans and the
TiO2/ESP function
01: Support 2-pipe proportional control valves and 3-speed fans
02: Support 2-pipe proportional control valves, ECM fans and
the TiO2/ESP function
03: Support 4-pipe on-off 3-wire valves and ECM fans
04: Support 4-pipe on-off 2-wire valves, ECM fans and the
TiO
2
/ESP function
05: Support 4-pipe proportional control valves and 3-speed fans
T7700-TF60-9MS0:
00: Support 2-pipe on-off 2/3-wire valves, ECM fans, Modbus
RTU communication and the TiO
2
/ESP function
01: Support 2-tube proportional control valves, 3-speed fans
and Modbus RTU communication
02: Support 2-pipe proportional control valves, ECM fans,
Modbus RTU communication and the TiO
2
/ESP function
03: Support 4-pipe on-off 3-wire valves, ECM fans and Modbus
RTU communication
04: Support 4-pipe on-off 2-wire valves, ECM fans, Modbus
RTU communication and the TiO
2
/ESP function
05: Support 4-pipe proportional control valves, 3-speed fans
and Modbus RTU communication
T7300-TF61-9MS0:
00: Support 2-pipe on-off 2/3-wire valves, ECM fans and the
TiO2/ESP function
01: Support 2-pipe proportional control valves and 3-speed fans
02: Support 2-pipe proportional control valves, ECM fans and
the TiO2/ESP function
03: Support 4-pipe on-off 3-wire valves and ECM fans
04: Support 4-pipe on-off 2-wire valves, ECM fans and the
TiO
2
/ESP function
05: Support 4-pipe proportional control valves and 3-speed fans
All
T7000e English