Parameter
Item
Parameter Name
Parameter Setting
Range
(Default Value)
Functional Meaning Applicable Model
P7 Software version / U00~99 (U12 stands for the V12 version.) All
H0
Set the lower
temperature limit
5℃(41°F Setting range: 0-48.5 (32-120°F) All
H1
Set the upper
temperature limit
35℃(95°F Setting range: 1-49.5 (33-121°F) All
H2 Temperature offset 0℃(0°F Setting range: -5-5 (-9-9°F) All
H3
Backlight turn-on time
setting
20 Setting range: 5-99 seconds All
H4
Backlight brightness
setting
80 Setting range: 10-100% All
H5
Operational mode
selection
00
00-Cooling/Heating/Ventilation
All
01-Cooling/Ventilation
02-Heating/Ventilation
03-Cooling/Heating/AUTO/Ventilation (only for the 4-pipe system)
H6 Restore defaults 00
00: Not restore
All
01: Restore
After being restored, it is automatically set to 00.
H7 Communication address 01 Setting range: 1-64 T7700
H8 Baud rate setting 00
00: 9600 bps
T7700
01: 4800 bps
E0
Set value of cooling in
the unoccupied state
26℃(79°F Setting range: 26-32 (72-90°F) All
E1
Set value of heating in
the unoccupied state
18℃(64°F Setting range: 10-21 (50-70°F) All
E2 Key lock (on/off key) 00
00: Unlocked
All
01: Locked
E3 Key lock (mode key) 00
00: Unlocked
All
01: Locked
E4 Key lock (fan speed key) 00
00: Unlocked
All
01: Locked
E5 Key lock (up/down key) 00
00: Unlocked
All
01: Locked
E6
Low temperature
protection
00
00: Disabled
All
01: Enabled
E7
Set value of low
temperature protection
5℃(41°F Setting range: 1-10 (34-50°F) All
E8 Set filter's service time 0
0 indicates that the filter's timekeeping is turned off, 10
indicates that the filter's service time is 1,000 hours, and 22
indicates that the filter's service time is 2,200 hours.
All
E9
Reset the filter's service
time and reminder
00
00: Not reset; 01: Reset
After being reset, it is automatically set to 0.
All
F0
Fan mode after reaching
the set temperature
under the automatic air
velocity
00
00: Run at a low air velocity.
All
01: Turn off the fan.
F1
Time to delay turning off
the fan
0
Setting range: 0-100 seconds
Under the automatic air velocity gear, the time to delay turning
off the fan after it meets the corresponding conditions.
All
F2
Fan mode in the
unoccupied state
00
00: Turn off the fan. All
01: Run at low speed
FAN-8941(1123)
T7000e English