TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
19
Configuring Occupancy
The TEC3000 controller supports a wide variety of occupancy sources to adapt to nearly any application.
Local stand-alone weekly scheduler
Remote schedule from BAS
Occupancy sensor (internal or remote)
Occupancy binary input (configurable)
Manual occupancy override
Temporary occupancy (by interacting with screen while unoccupied)
Temporary occupancy binary input
Occupancy is determined using a top-down decision matrix as shown in Table 6.
Occ Setpoint Select =
Setpoint Offset and
Heat Cool Setpoint Mode =
Common Setpoint
In this mode, the TEC has one setpoint, Common Setpoint, for heating and cooling. There is
also a common Setpoint Offset (warmer/cooler adjust) that is only applied to Common
Setpoint. Otherwise, this setting works the same as when Occ Setpoint Select = Setpoint
Offset and Heat Cool Setpoint Mode = Individual Setpoints.
Occ Setpoint Select = Min
and Max Setpoints and
Heat Cool Setpoint Mode =
Common Setpoint
In this mode, the TEC has one setpoint, Common Setpoint, for heating and cooling. There is
a configurable range for Common Setpoint, Min Setpoint, and Max Setpoint.
Table 5: Setpoint Operation
Mode of Setpoint
Operation
Details