EasyManuals Logo

Johnson Controls WT-4002-MCR User Manual

Johnson Controls WT-4002-MCR
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats Installation Instructions
11
6. Press to confirm the selection.
7. Change the setpoint pressure as desired
(Figure 11).
a. Press the Up button to increase the
branch line pressure at setpoint. The valid
range is 1 to 22 psig (7 to 152 kPa), adjustable
in increments of 0.5 psig (3 kPa). The default
setting is 9 psig (62 kPa).
b. Press the Down button to decrease the
branch line pressure at setpoint.
8. Press to confirm the selection.
9. Change the gain/sensitivity as desired
(Figure 12).
a. Press the Up button to increase the
gain/sensitivity. The valid range is 1 to 5 psi/F°
(13 to 65 kPa/C°), adjustable in increments of
0.5 psig (3 kPa). The default setting is 2 psi/F°
(26 kPa/C°).
b. Press the Down button to decrease the
gain/sensitivity.
10. Press to confirm the selection.
11. Change the proportional band – proportional
range/throttling range as desired (Figure 13).
a. Press the Up button to increase the
proportional band – proportional range/
throttling range. The valid range is 0 to 10F°
(0 to 6C°), adjustable in increments of 1F°
(0.6C°). The default setting is 6F° (3.6C°).
b. Press the Down button to decrease the
proportional band – proportional range/
throttling range.
12. Press to confirm the selection.
13. Change the unoccupied mode pressure as
desired (Figure 14).
a. Press the Up button to increase the
branch line pressure during Unoccupied Mode
periods. The valid range is 0 to 22 psig (0 to
152 kPa), adjustable in increments of 0.5 psig
(3 kPa). The default setting is 0 psig (0 kPa).
b. Press the Down button to decrease the
branch line pressure during Unoccupied Mode
periods.
FIG:drct_actng
SPPsi

9.0
Gain

2.0
PropBnd

6.0
UnocPsi 0.0
DirActing
Figure 11: Changing the Setpoint Pressure
+
-
FIG:gain
SPPsi

9.0
Gain


2.0
PropBnd

6.0
UnocPsi
0.0
DirActing
Figure 12: Changing the Gain/Sensitivity
+
-
FIG:prprtnl_bnd
SPPsi

9.0
Gain

2.0
PropBnd

6.0
UnocPsi 0.0
DirActing
Figure 13: Changing the Proportional Band –
Proportional Range/Throttling Range
+
-
FIG:unoccpd_mde_prssr
SPPsi

9.0
Gain

2.0
PropBnd

6.0
UnocPs i
0.0
DirActing
Figure 14: Changing the Unoccupied Mode
Pressure
+
-

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls WT-4002-MCR and is the answer not in the manual?

Johnson Controls WT-4002-MCR Specifications

General IconGeneral
BrandJohnson Controls
ModelWT-4002-MCR
CategoryThermostat
LanguageEnglish

Related product manuals