5-32
SM-18003
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(87) Motion Sensor Detection Level (K5)
Thisfunctionisutilizedtodeterminetheamountofhumanactivitydependingonthereactionrateasin
thefollowingtable.
When“HIGH”(01)isset,thethresholdoftheamountofhumanactivityissmallerthanthestandard.
Astheresult,thedetectionlevelofhumansensorbecomeshigher.
When“LOW”(02)isset,thethresholdoftheamountofhumanactivityislargerthanthestandard.
Asaresult,thedetectionlevelofhumansensorbecomeslower.
Setting
Conditions
Amountof
HumanActivity
00(FactorySetting) 01 02
Standard HighSensitive LowSensitive
ExtraLarge
80% < Reaction Rate 60% < Reaction Rate 80% < Reaction Rate
Large
30% <ReactionRate˂80% 20% <ReactionRate˂60% 40% <ReactionRate˂80%
Small 3% < Reaction Rate < 30% 3% < Reaction Rate < 20% 3% < Reaction Rate < 40%
NoAvailable
Reaction Rate < 3% Reaction Rate < 3% Reaction Rate < 20%
(88) Operation Setting during Thermistor of Wired Controller or Remote Sensor (K6)
Thisfunctionisutilizedtochangethefunction"ThermistorofWiredController/RemoteSensor(C8)"
accordingtooperationmode.
SettingCondition Operation Mode
00 ALL
01 COOL/DRY
02 HEAT
03 sameas"00"
NOTE:
AllmodesareavailableduringautomaticCool/Heatoperationmode.
(89) Radiation Temperature Correction (K7)
Thisfunctionisutilizedtocorrecttheradiationtemperaturedetectedhigher/lowerthanactualradiation
temperaturedependingontheenvironment.
SettingCondition Operation Mode
00(Standard) 0
o
F (0
o
C)
01(Upward) +3
o
F(+2
o
C)
02(Downward) -3
o
F (-2
o
C)
(90) Control of Dew Condensation Prevention (K8)
CondensationmayoccuraroundairoutletduringCOOL/DRYoperationwithhorizontalairowand
downwardairowforlongtimeperiod.
Thisfunctionisutilizedtopreventcondensationbymovingthelouverswingangletothethirdstep
automaticallyfor30minutesevery1hour.
(91) Not Prepared (K9)
(92) Not Prepared (KA)