JOHNSON CONTROLS
20
FORM 150.62-NM6 (103)
OVER CURRENT PROTECTION,
UNIT VOLTAGE UNIT VOLTAGE CONTROL POWER
MCA
SEE NOTE B NF DISC SW
NOTE A MIN MAX
MODELS w/o
CONTROL TRANS
115-1-60/50 15A 10A 15A 30 A / 240V
-17 200-1-60 15A 10A 15A 30 A / 240V
-28 230-1-60 15A 10A 15A 30 A / 240V
MODELS w/
-40 380-1-60 15A 10A 15A 30 A / 480V
CONTROL TRANS
-46 460-1-60 15A 10A 15A 30 A / 480V
-58 575-1-60 15A 10A 15A 30 A / 600V
A. Minimum #14 AWG, 75°C, Copper Recommended
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker
ELECTRICAL DATA
Installation
TABLE 1 – MICRO PANEL POWER SUPPLY
It is possible that multiple sources of power can be supplying the unit power panel. To prevent
serious injury or death, the technician should verify that NO LETHAL VOLTAGES are
present inside the panel AFTER disconnecting power, PRIOR to working on equipment.
The unit evaporator heater uses 120VAC. Disconnecting 120VAC power from the unit, at
or below freezing temperatures, can result in damage to the evaporator and unit as a result
of the chilled liquid freezing.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls York YCAL0124E Series and is the answer not in the manual?

Johnson Controls York YCAL0124E Series Specifications

General IconGeneral
BrandJohnson Controls
ModelYork YCAL0124E Series
CategoryChiller
LanguageEnglish

Related product manuals