JOHNSON CONTROLS
12
FORM 160.69-N2
ISSUE DATE: 7/31/2015
SECTION 1 - INTRODUCTION
NEOPRENE ISOLATORS
*
*
B
FIGURE 3 - NEOPRENE ISOLATORS
SHELL CODE UNIT WEIGHT DIM "A" DIM "B" DIM "C" DIM "D" QTY
B B Up to 130,000 lbs (58,967 Kgs) 10' 3" (3124)
8 x 1"
from edge.
11" (279) 12 (305) 8
C C Up to 225,000 lbs (102,060 Kgs) 11' 5" (3176) 11" (279) 10" (254) 8
D D Up to 225,000 lbs (102,060 Kgs) 12' 9" (3887) 11" (279) 10" (254) 8
E E Up to 280,000 lbs (127,005 Kgs) 12' 9" (3887) 11" (279) 12 (305) 8
F F Up to 280,000 lbs (127,005 Kgs) 13' 9" (4192) 11" (279) 12 (305) 8
G G Up to 280,000 lbs (127,005 Kgs) 13' 9" (4192) 11" (279) 12 (305) 8
H H Up to 280,000 lbs (127,005 Kgs) 14' 8" (4471) 11" (279) 12 (305) 8
K K Up to 280,000 lbs (127,005 Kgs) 14' 8" (4471) 11" (279) 12 (305) 8
Approx weight including motor and 150# compact water boxes.
LD12643a
* Typical both ends.