SECTION 1 - INTRODUCTION
TABLE 1 - EVAPORATOR CONDENSER SHELL CODES
SHELL B B C C D D E E F F G G H H K K
A
11' 5"
(3,480)
12'-6"
(3,810)
13'-6"
(4,115)
13'-6"
(4,115)
14'-6 1/4"
(4,426)
14'-6 1/4"
(4,426)
15'-5 1/4"
(4,705)
15'-6"
(4,724)
B
12'-1 3/4"
(3,683)
12'-10"
(3,759)
13'-0"
(3,962)
13'-0"
(3,962)
13'-8"
(4,166)
13'-8"
(4,166)
14'-2"
(4,318)
16'-0"
(4,877)
C
2'-8"
(813)
2"-11 1/2"
(914)
3'-5"
(1,041)
3'-5"
(1,041)
3'-9"
(1,143)
3'-9"
(1,143)
4'-0"
(1,219)
4'-0"
(1,219)
D
2'-5 1/2"
(749)
2'-9"
(826)
2'-11 1/2"
(902)
2'-11 1/2"
(902)
3'-1 1/2"
(953)
3'-1 1/2"
(955)
3'-4"
(1,016)
3'-4"
(1,016)
E
18'-0"
(5,486)
22'-0"
(6,706)
18'-0"
(5,486)
22'-0"
(6,706)
18'-0"
(5,486)
22'-0"
(6,706)
18'-0"
(5,486)
22'-0"
(6,706)
F
2'-0 3/4"
(629)
1'-10"
(629)
2'-1"
(635)
2'-1"
(635)
2'-3"
(686)
2'-3"
(686)
2'-3 9/16"
(700)
2'-3 9/16"
(700)
G
1'-4 3/4"
(425)
1'-1 5/8"
(425)
1'-4 1/4"
(413)
1'-4 1/4"
(413)
1'-6 1/4"
(464)
1'-6 1/4"
(464)
1'-6 7/8"
(479)
1'-6 7/8"
(479)
H
0'-11 11/16"
(297)
1'-1 3/4"
(297)
1'-2 5/8"
(371)
1'-2 5/8"
(371)
1'-3 5/8"
(397)
1'-3 5/8"
(397)
1'-4 1/4"
(413)
1'-4 1/4"
(413)
J
1'-7 5/8"
(498)
1'-9 1/4"
(498)
2'-1 1/2"
(648)
2'-1 1/2"
(648)
2'-2"
(660)
2'-2"
(660)
2'-1"
(635)
2'-1"
(65)
L
5'-1 1/2"
(1,562)
5'-8 1/2"
(1,740)
6'-4 1/2"
(1,943)
6'-4 1/2"
(1,943)
6'-10 1/2"
(2,096)
6'-10 1/2"
(2,096)
7'-4"
(2,235)
7'-4"
(2,235)
NOTES:
1. All dimensions are approximate. Certied dimensions are
available on request.
2. For compact water boxes (shown above), determine overall unit length
by adding water box depth to tube sheet length.
3. Water nozzles can be located on either end of unit. Add 1/2" to nozzle
length for anges connections.
4. To determine overall height, add dimension "M" for the
appropriate isolator type.
5. Use of motors with motor hoods may increase overall unit dimensions.
UNIT DIMENSIONS
ADDITIONAL OPERATING HEIGHT
CLEARANCE TO FLOOR
TYPE OF CHILLER MOUNTING FT.-IN. MM
Neoprene Pad Isolators 1-3/4" 44
Spring Isolators 1" Deection 1" 25
Direct Mount 3/4" 19