035-19569-101 (0109)
3-3
GB
3.4 Rigging
The complete standard chiller is shipped without skids.
(When optional skids are used it may be necessary to
remove the skids so riggers skates can be used under
the unit end sheets to reduce overall height.)
Each unit has four (4) lifting holes (two in each end) in
the end sheets which should be used to lift the unit.
Care should be taken at all times during rigging and
handling of the chiller to avoid damage to the unit and
its external connections. Lift only using holes shown.
CAUTION
Do not lift the unit with slings around motor/
compressor assembly or by means of eye
bolts in the tapped holes of the compressor
motor assembly. Do not turn a unit on its side
for rigging. Do not rig vertically.
The rigging and operating weights and overall dimensions
are given in Section 9 as a guide in determining the
clearances required for rigging. (Add 150 mm to overall
height for optional skidded unit.).
Figure 3.1 . Rigging