Why is the discharge pressure abnormally high in my Johnson Controls York YK?
- EEric PetersenAug 16, 2025
Abnormally high discharge pressure in your Johnson Controls Industrial Equipment can be due to several reasons. It could be that there is air in the condenser. Other potential causes include dirty or scaled condenser tubes, which would require cleaning the condenser tubes and checking the water conditioning. It may also be caused by high condenser water temperature, so reduce the condenser water inlet temperature and check the cooling tower and water circulation. Finally, insufficient condensing water flow could be the culprit; in this case, increase the quantity of water through the condenser to the proper value.