9.5 Nozzle Arrangements - Condenser Compact Water Boxes
FLOOR
LINE
FLOOR
LINE
FLOOR
LINE
COMPRESSOR END
MOTOR END
COMPRESSOR END
MOTOR END
COMPRESSOR END
MOTOR END
MM
COND. COND.
COND. COND.
COND. COND.
FRONT
OF UNIT
FRONT
OF UNIT
FRONT
OF UNIT
1-PASS
2-PASS
3-PASS
P
Q
SU
R
T
W
Y
VX
MM
MM
D D
D D
D D
BBBB
BBBB
DD
DD
DD
DD
CCCC
NOZZLE
ARRANGEMENTS
NO. OF
PASSES
COND.
IN OUT
1
PQ
QP
NOZZLE
ARRANGEMENTS
NO. OF
PASSES
COND.
IN OUT
2
RS
TU
NOZZLE
ARRANGEMENTS
NO. OF
PASSES
COND.
IN OUT
3
VY
XW
NOTES:
1. Standard water nozzles are furnished as welding stub-outs with Victaulic grooves, allowing the option of welding, anges, or use of Victaulic
couplings. Factory-installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1.6 mm raised face), water anges nozzles are
optional (add 13 mm to nozzle length). Companion anges, nuts, bolts, and gaskets are not furnished.
2. One, two and three pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of evaporator nozzles may
be used in combination with any pair of condenser nozzles.
3. Evaporator and condenser water must enter the water box through the bottom connection to achieve rated performance.
4. Connected piping should allow for removal of compact water boxes for tube access and cleaning.
5. Add dimension "M" as shown on the unit dimensions page for the appropriate isolator type.
6. Standard 150 psi (1034 kPa) design pressure water boxes shown.
COMPACTWATER BOXES - 150 PSI ROUND
CONDENSER
SHELL CODE
NOZZLE PIPE SIZE(IN)
NO. OF PASSES 1-PASS 2-PASS 3-PASS
123DCC
5
BB
5
DD
5
BB
5
DD
5
A
10 6 6 381 711 546 876 546 876
C,D
12 8 6 394 762 568 956 568 956
E,F
14 10 8 445 813 603 1022 603 1022
J,K,L
16 10 10 508 914 686 1143 686 1143
M,N
20 14 10 584 1067 772 1362 772 1362
P, Q
20 16 14 641 1118 787 1448 787 1448
R,S
20 18 14 699 1181 851 1511 851 1511
T, V,W
24 18 16 749 1207 838 1575 838 1575
X,Z
24 20 16 813 1251 845 1657 845 1657