JUNCTEK
circuit and activate the protection function.
18).Undervoltage protection: 0.00-120.00V
In the system setting interface, press the 【▲】【▼】 buttons to switch to
undervoltage protection setting. Press the 【OK】 button to select the value,
use the
【
▲
】【
▼
】
buttons to change the value, press the
【
OK
】
button to
switch the digit, and switch from the smallest digit to the highest digit. Press
the 【 OK 】 button again when in the highest digit to confirm the set
undervoltage protection value.
If the value is 000.00V, the protection function is not activated. If the value is
greater than 000.00V, the protection function will be activated. If the current
voltage is less than the set undervoltage protection value, the screen will
display LVP in the upper left corner, indicating that the protection function is
activated.
The protection function requires the purchase of a relay. If there is no
relay, do not set the value. Install the relay in the circuit to disconnect the
circuit and activate the protection function.
19).Charging overcurrent protection: 0-100A/400A/600A (depending on the
machine model)
In the system setting interface, press the
【
▲
】【
▼
】
buttons to switch to
charging overcurrent protection setting. Press the 【OK】 button to select the
value, use the【▲】【▼】buttons to change the value, press the【OK】button
to switch the digit, and switch from the smallest digit to the highest digit. Press
the
【
OK
】
button again when in the highest digit to confirm the set charging
overcurrent protection value.
If the value is 000.00A, the protection function is not activated. If the value is
greater than 000.00A, the protection function will be activated. If the current
charging current is greater than the set charging overcurrent protection value,
the screen will display NCP in the upper left corner, indicating that the
protection function is activated.
The protection function requires the purchase of a relay. If there is no
relay, do not set the value. Install the relay in the circuit to disconnect the
circuit and activate the protection function.
20).Discharge overcurrent protection: 0-100A/400A/600A (depending on the
machine model)
In the system settings interface, press the 【▲】【▼】buttons to switch to the
discharge overcurrent protection setting. Short press the 【 OK 】 button to
select the value. Press the
【
▲
】【
▼
】
buttons to change the value, and press
the
【
OK
】
button to switch the digit from the smallest to the highest. When the
highest digit is reached, press the 【 OK 】 button again to confirm the
discharging overcurrent protection setting.
If the value is 000.00A, the protection function is not activated. If the value is
greater than 000.00A, the protection function is activated. If the current
discharge current is greater than the set discharge overcurrent protection
value, OCP will be displayed in the upper left corner of the screen, indicating
that the protection is active.