36 Kmstrup A/S • 5512853_C1_GB_01.2017
M-Bus Mster MultiPort 250D
Legcy Dely
If the mster is connected to old genertions of Kmstrup M-Bus modules nd secondry ddressing is used, Legcy
Dely shll be min. 15 seconds.
Legcy Dely ensures tht the modules re redy to reply to the mster when n NKE commnd is sent from the
mster.
The bove is vlid for the following M-Bus modules:
• 6604 nd 6607 modules for MULTICAL® III
• 6608 nd 6609 modules MULTICAL® 66CDE
• 660S module for MULTICAL® Compct nd MULTICAL® 401
Timing Profile
If no repeters re connected to the mster, the scnning speed cn be set to Fst which improves the scnning speed
during meter serch.
Timing Dely
Bud Chnge Dely
Bud Chnge Dely sets how long the mster must puse scnning when
switching to nother bud rte in the menu Scn All Bud.
Bud Chnge Dely is per defult 700 ms.
Bus Collision Dely
Bus Collision Dely sets how long the mster must puse before continuing scnning fter collision between
number of M-Bus ddresses.
Collision Dely is per defult 700 ms.
Bus Overlod Dely
Bus Overlod Dely sets the dely of the internl scnner function fter hving detected n overlod on the M-Bus
outputs. This cn e.g. be cused by too mny connected meters or short-circuit in the cble network.
Overlod Dely is per defult 700 ms.