M-Bus Mster MultiPort 250D
Legcy Dely
If the mster is connected to old genertions of Kmstrup M-Bus modules nd secondry ddressing is used, Legcy
Dely shll be min. 15 seconds.
Legcy Dely ensures tht the modules re redy to reply to the mster when n NKE commnd is sent from the
mster.
The bove is vlid for the following M-Bus modules:
6604 nd 6607 modules for MULTICAL® III
6608 nd 6609 modules MULTICAL® 66CDE
660S module for MULTICAL® Compct nd MULTICAL® 401
Timing Profile
If no repeters re connected to the mster, the scnning speed cn be set to Fst which improves the scnning speed
during meter serch.
Timing Dely
Bud Chnge Dely
Bud Chnge Dely sets how long the mster must puse scnning when
switching to nother bud rte in the menu Scn All Bud.
Bud Chnge Dely is per defult 700 ms.
Bus Collision Dely
Bus Collision Dely sets how long the mster must puse before continuing scnning fter  collision between 
number of M-Bus ddresses.
Collision Dely is per defult 700 ms.
Bus Overlod Dely
Bus Overlod Dely sets the dely of the internl scnner function fter hving detected n overlod on the M-Bus
outputs. This cn e.g. be cused by too mny connected meters or short-circuit in the cble network.
Overlod Dely is per defult 700 ms.