Rev. 1.00
22585_EDEBDA0252-0318-1_EN
11
KBR multicomp F144-3 6DO/12DOControl and display panel
General notes on operating the sensor buttons:
U button Start conguration and reset input
V button Change values during conguration
W button Navigate through submenus
X button Navigate through main menus and save button during conguration
Button combinations:
U and V Delete accumulated values and reset the system
Default controller settings after reset:
Consumption target cos phi: 0.95 inductive
Recovery target cos phi: 1.00 (cannot be changed)
Alarm cos phi: 0.92 inductive
Main transformer current: Primary current 1000 A
Secondary current 5 A
Measuring voltage: Primary voltage 400 V Ph-Ph
(corresponds to 230V Ph-N )
Secondary voltage 400 V Ph-Ph
(corresponds to 230V Ph-N )
Rot. eld U: L1-N
Rot. eld I: L1
Current attenuation coecient: 0
Voltage attenuation coecient: 0
Attenuation coecient Qmiss: 0
Alarm delay: 20 minutes (1200 s)
Idle time: 30 ms
Switching interval: 50 ms
Hysteresis connection: 100% of lowest stage power
Hysteresis switch-o: 100% of lowest stage power
Operating cycle count: active
Stage switching mode: Automatic
Sampling rate: Automatic
Harmonics monitoring: Activated by set limit
Limit THD 8%