Rev. 1.00
22585_EDEBDA0252-0318-1_EN
12
KBR multicomp F144-3 6DO/12DO
Stage power: Not set
Max. stage power per switching cycle: 0 kvar
Stage power monitored: Deactivated
Discharge time: 20 ms
Password: No password (9999, meaning all functions
are accessible)
Language display: English
Contrast setting: 5
Brightness setting: 5
Dimmer brightness: 0
Light load limit: 15 mA
Light load delay: 60 minutes
Temperature measurement: On
Output 6/12 as stage or fan: Fan output
Fan switch-on temperature: > 28 °C
Fan switch-o temperature: < 23 °C
System switch-o temperature: > 48°C
System switch-on temperature: < 43°C
Learning mode menu display: O
Touch tones: On
Error message dialog after reset:
No measuring voltage: Message and alarm relay
No stage power: Message and alarm relay
PFC too small: Message and alarm relay
THD too high: Message and alarm relay
No measuring current: Message and alarm relay
Light load operation: Message and alarm relay
Temperature switch-o: Message and alarm relay