Rev. 1.00
22585_EDEBDA0252-0318-1_EN
13
KBR multicomp F144-3 6DO/12DO
The controls in the compensation systems are preset.
The following parameters need to be checked or set:
Target cos phi in accordance with the electricity supplier regulations
(for kVA tari cos phi = 1)
Primary current and secondary current in accordance with input current
transformer.
Voltage transformer ratio, if required
NOTE
Upon delivery, the bus protocol is set to: Modbus RTU, baud rate 38400, parity
even
This setting can only be changed manually on the device.
Performing a "Reset to default settings" has no e ect on changed settings.