KBR multicomp F144-3 6DO/12DODescription of the display window
The same applies for deactivation in case of overcompensation.
If the stage power limit is set lower than the value of the largest existing stage,
but larger than "0", the controller automatically uses the largest capacitor stage
available.
If the maximum stage power is set to "0", this function is deactivated and the
controller switches each capacitor stage individually.
NOTE
If stage monitoring is activated, set a switching interval and idle time of 1000
ms each to prevent measurement errors caused by switching operations in
quick succession. Additionally, we recommend setting the maximum stage
power to "0" to prevent simultaneous switching of stages.
Con guring the capacitor stages:
There are two ways of con guring the capacitor stages. The stages can be con-
gured manually or using the auto con guration mode. It is important to set
the stage power correctly. The stage power is shown on the nameplate of the
stage and on the circuit diagram
and can be con gured manually. In this case, skip the menu item "Learning
mode activate" and enter the power value individually for each stage.
NOTE
If you cannot select the Learning mode menu item, check whether menu "On"
is selected for "Learning mode" in the "Extras" menu. After the learning process
has been completed, all stages are switched to automatic mode.