Operating instructions multicomp
Version 1.00 Page 25 of 29
EDEBDA0144 / 0511-1 GB
10 Setting range of the parameters configurable
Primary voltage 1 V to 39999 V Ph-Ph
Secondary voltage 1 V to 999 V Ph-Ph
Primary current 1 A to 39999 A
Secondary current 1 and 5 A
Rot.field U L1N, L2N, L3N, L12, L23, L31
Rot.field I L1, L2, L3, -L1, -L2, -L3
Consumption target CosPhi ind. 0.80 to cap. 0.80
Recovery target CosPhi ind. 1.0 (cannot be set)
FTS Alarm CosPhi ind. 0.70 to 1.0
Attenuation coefficient current 0 to 9
Attenuation coefficient voltage 0 to 9
Attenuation coefficient Qmiss 0 to 9
Idle time 0 to 300 sec.
Alarm relay time 0 to 3000 sec.
Hysteresis connection 70 to 150 %
Hysteresis disconnection 70 to 150 %
Switching interval 0 to 10 sec.
Limit switching cycles 0 to 999999
Stage power 0 to 999.9 kvar
Discharge time 0, 3, 30, 60, 90, 300, 600, 900 sec.
Stage switching mode = Automatic, manual off, manual on
Stage power monitoring Deactivatable
Harmonics monitoring Deactivatable (0%)
THD limit 0 to 10%
Scanning frequency Automatic, fixed 50 Hz, fixed 60 Hz
Password No password (9999, meaning all functions are accessible)
Display language German, English, French or Spanish
Contrast settings 0 to 10
Error message dialog:
Missing measurement voltage The settings Message or alarm relay /
Missing measurement current Message and error relay / Off
Missing stage power is identical for all errors!
Facility too small
THD too high
Switching cycle limit exceeded
Light load operation
Error message dialog after reset:
Missing measurement voltage Alarm relay
Missing current Message
Missing stage power Alarm relay
FTS (Facility Too Small) Message and alarm relay
THD too high Alarm relay
Switching cycle limit exceeded Alarm relay
Light load operation Off