EasyManua.ls Logo

KBR multisys D2-ESET/MSMT-4 - LAN and KBR Module Bus Interfaces (Multisys D2-BSET-4)

Default Icon
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V4.00
25833_EDEBDA0290-0622-1_EN
7
Interfaces LAN and KBR module bus
LAN
RJ-12
1 2 3
ON
SAB
4
Netz
2.2 LAN and KBR Module Bus Interfaces (multisys D2-BSET-4)
The Modbus interface is set to the Modbus parameters 38,400 baud, 8 data bits, parity
even, 1 stop bit. If necessary, it can be terminated using four DIP switches.
LED for monitoring power supply
Power supply
<10VA; 100 - 240V ±10% DC/50/60 Hz
(2-pole multi-pin connector, 5 mm)
RJ-12 for the KBR module bus
DIP switch for terminating RJ-12:
DIP1 and DIP2 ON, DIP3 OFF = failsafe activated
DIP1 and DIP2 OFF, DIP3 ON = termination activated
DIP1 and DIP2 OFF, DIP3 OFF= no failsafe,
no termination, DIP4 switches the 24V supply
voltage at RJ12.
NOTE
The failsafe termination can only be activated once
per bus segment!
RJ-45 Ethernet connection
The operating status of the LAN interface (E-Port) is indicated by two LEDs:
Connection LED (left)
O No connection
Green 10 / 100 Mbits
Activity LED (right)
O No Data
Yellow Data