V4.00
25833_EDEBDA0290-0622-1_EN
7
Interfaces LAN and KBR module bus
LAN
RJ-12
1 2 3
ON
SAB
4
Netz
2.2 LAN and KBR Module Bus Interfaces (multisys D2-BSET-4)
The Modbus interface is set to the Modbus parameters 38,400 baud, 8 data bits, parity
even, 1 stop bit. If necessary, it can be terminated using four DIP switches.
LED for monitoring power supply
Power supply
<10VA; 100 - 240V ±10% DC/50/60 Hz
(2-pole multi-pin connector, 5 mm)
RJ-12 for the KBR module bus
DIP switch for terminating RJ-12:
DIP1 and DIP2 ON, DIP3 OFF = failsafe activated
DIP1 and DIP2 OFF, DIP3 ON = termination activated
DIP1 and DIP2 OFF, DIP3 OFF= no failsafe,
no termination, DIP4 switches the 24V supply
voltage at RJ12.
NOTE
The failsafe termination can only be activated once
per bus segment!
RJ-45 Ethernet connection
The operating status of the LAN interface (E-Port) is indicated by two LEDs:
Connection LED (left)
O No connection
Green 10 / 100 Mbits
Activity LED (right)
O No Data
Yellow Data