23
CP-Parameter
CP.22 DC braking / Mode
With DC-braking the motor is not decelerated by the ramp. Quick braking is caused by
D.C. voltage, which is applied onto the motor winding. This parameter determines how the
dc-braking is triggered.
Value Activation
0 DC-braking deactivated
1 DC-braking at switch off of the direction of rotation and upon reaching 0 Hz.
The braking time is CP.23 or until the next direction of rotation.
2* DC-braking as soon as setting for the direction of rotation is absent.
3* DC-braking as soon as the direction of rotation changes or is absent.
4* DC-braking on disabling the direction of rotation and if the real frequency falls
below 4 Hz.
5* DC-braking when the real frequency falls below 4 Hz and the drives
decelerates
6* DC-braking as soon as the set value falls below 4 Hz.
7* DC-braking when input I4 is switched. At control circuit B = value "0"
8 DC-braking as long as input I4 is switched. At control circuit B = value "0"
9 DC-braking after switching on the modulation on.
* Braking time depends on the actual frequency.
CP.26 Speed search condition
When connecting the frequency inverter onto a decelerating motor, an error can be
triggered by the differing rotating field frequencies. With activated speed search the
inverter searches for the actual motor speed, adapts its output frequency and accelerates
with the adjusted ramp to the given set value. During speed search CP.3 displays "SSF".
The parameter determines, under what conditions the functions operate.
In case of several conditions the sum of the value must be entered. Example: CP.26 =
12 means after reset and after auto-reset UP.
Value Condition
0 Function off
1 at control release
2 at switch on
4 after reset
8 after Auto-Reset UP
This function protects the frequency inverter against switch off through overcurrent
during constant output frequency. When exceeding the adjusted value, the output
frequency is reduced until the value drops below the adjusted value. CP. 3 displays "SSL"
at active function.
This function protects the frequency inverter against switching off through overcurrent
during the acceleration ramp. When the ramp reaches the adjusted value,it is stopped
so long until the current decreases again. CP.3 displays "LAS" at active function.
CP.25 Max. constant current
CP.24 Max. ramp current

Other manuals for KEB COMBIVERT F5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 and is the answer not in the manual?

KEB COMBIVERT F5 Specifications

General IconGeneral
CategoryDC Drives
Enclosure RatingIP20
Control ModeVector Control, V/f Control
ProtectionOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Fieldbus CommunicationPROFIBUS, CANopen
Communication InterfacesRS-485
Input Voltage380-480V AC
Cooling MethodForced air cooling (fan)

Related product manuals