Product description
2.3 Technical data
2.3.1 230 V class
05 07 09 10
BBBB
13 1 31313
[kVA] 0,9 1,6 2,8 4
[kW] 0,37 0,75 1,5 2,2
[A] 2,3 4 7 10
[A] 4,1 7,2 12,6 18
[A] 5 8,6 15,1 21,6
[A] 4,6 3,2 8 5,6 14 9,8 20 14
[A] 16 20 16 20 16 25 20
[kHz] 16 16 16 8
[kHz] 16 16 16 16
[W] 50 65 90 105
[Ohm] 56 56 47 33
[Ohm] 180 180 100 68
[A] 7,5 7,5 9,5 12
[V] 180...260 ±0
[Hz] 50 / 60 ±2
[V] 230
[V] 3 x 0...U
N
[Hz] 0...400
[mm²] 1,5 1,5 1,5 2,5
[m] 30 100 100 100
[m] 20 50 100 100
[m] 10 20 40 100
Inverter Size
Housing size
Phas es
Output rated pow er
Max . r ated mot or pow e r
Output rated current
Max. short time current
OC-tripping current
Input rated current
Max. permissible mains fuse (inert)
Rated sw itching frequency
Max. sw itching frequency
Pow er loss at rated operation
Min. braking resistor
Typ. braking resistor
Max. braking current
Mains voltage U
N
Mains frequency
Input rated voltage
Output voltage
Output frequency
Min. mot or line c r os s s e c t ion
Max. motor line length (shielded) 4 kHz
Max. motor line length (shielded) 8 kHz
Max. motor line length (shielded) 16 kHz

Other manuals for KEB COMBIVERT F5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 and is the answer not in the manual?

KEB COMBIVERT F5 Specifications

General IconGeneral
CategoryDC Drives
Enclosure RatingIP20
Control ModeVector Control, V/f Control
ProtectionOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Fieldbus CommunicationPROFIBUS, CANopen
Communication InterfacesRS-485
Input Voltage380-480V AC
Cooling MethodForced air cooling (fan)