2.3.2 400 V class
Site altitude max. 2000 m. With site altitudes over 1000 m a derating of 1% per 100 m
must be taken into consideration.
Product description
1)
at mains voltage > 460 V multiply the nominal current with factor 0,86
05 07 09 10 12
BB B BB
33333
[kVA] 0,9 1,8 2,8 4 6,6
[kW] 0,37 0,75 1,5 2,2 4
[A] 1,3 2,6 4,1 5,8 9,5
[A] 2,3 4,7 7,4 10,4 17
[A] 2,8 5,6 8,9 12,5 21
[A] 1,8 3,6 6 8 13
[A]1616161620
[kHz] 16 16 8 8 4
[kHz]161616164
[W] 60 90 80 120 150
[Ohm] 390 120 120 82 82
[Ohm] 620 620 390 270 150
[A] 2,2 7,5 7,5 10 10
[V] 305...500 ±0
[Hz] 50 / 60 ±2
[V] 400
1)
[V] 3 x 0...U
N
[Hz] 0...400
[mm²] 1,5 1,5 1,5 1,5 2,5
[m] 10 10 100 100 50
[m] 8 8 30 50 -
[m] 4 5 10 10 -
Inverter Size
Housing size
Phas es
Output rated pow er
Max. rated motor pow er
Output rated current
Max. short time current
OC-tripping current
Input rated current
Max. permissible mains fuse (inert)
Rated sw itching frequency
Max. sw itching frequency
Pow er loss at rated operation
Min. braking resistor
Typ. braking resistor
Max. braking current
Mains voltage U
N
Mains frequency
Input rated voltage
Output voltage
Output frequency
Min. motor line cross section
Max. motor line length (shielded) 4 kHz
Max. motor line length (shielded) 8 kHz
Max. motor line length (shielded) 16 kHz

Other manuals for KEB COMBIVERT F5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 and is the answer not in the manual?

KEB COMBIVERT F5 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F5
CategoryDC Drives
LanguageEnglish

Related product manuals