EasyManua.ls Logo

KEB G6 - Annex a; Calculation of the Motor Voltage; Maintenance; A.1 Calculation of the Motor Voltage

KEB G6
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GB - 22
Annex
Annex A
A.1 Calculation of the motor voltage
The motor voltage for dimensioning of the drive is depending on the used components. The
mains voltage reduces according to the following table:
Mains choke Uk 4 % Example:
Inverter open loop 4 % Closed loop inverter with mains- and motor choke at
non-rigid supply system:
400 V mains voltage - 15 % = 340 V motor voltage
Inverter closed loop 8 %
Motor choke Uk 1 %
Non-rigid supply
system
2 %
A.2 Maintenance
All work may only be done by qualied personnel. The security must be ensured as follows:
Disconnect power supply at MCCB
Secure against restarting
Await discharge time of capacitors
(if necessary controlling by measurement at „+“ and „-“, respectively at „++“ and „--“)
Ensure loss of voltage by measurement
In order to avoid premature ageing and avoidable malfunctions, the measures mentioned
below must be carried out in the appropriate cycle.
Cycle Function
Constant
Pay attention to unusual noises of the motor (e.g. vibrations) as well as of the
frequency inverter (e.g. fan).
Pay attention to unusual smells of the motor or frequency inverter (e.g. evapo-
ration of capacitor electrolyte, braise of the motor winding).
Monthly
Check unit for loose screws and plugs and if necessary tighten up.
Clean frequency inverter from dirt and dust deposits. Pay attention especially
to cooling ns and protective grid of the fans.
Examine and clean extracted air lter and cooling air lter of the control cabi-
net.
Examine function of the fans of the KEB COMBIVERT. The fan must be repla-
ced in case of audible vibrations or squeak.
Make a visual leak test of the cooling circuit for water-cooled inverters.

Table of Contents

Related product manuals