KC-P30 Connections and wiring
Installation manual V3.28
35
© KEBA
RFID DSW 1.1 Description
On ON
P30 b-series and c-series (without charging network)
Charging enabled with X1 closed AND correct RFID authoriza-
tion.
If no RFID cards have been taught in, charging takes place with
a closed X1.
On OFF
P30 c-series (in a charging network) and x-series
Charging enabled with correct RFID authorization.
No access is possible without an RFID card.
On ON
P30 c-series (in a charging network) and x-series
Charging enabled with X1 closed AND correct RFID authoriza-
tion.
No access is possible without an RFID card.
7.4.1 Connection diagram
Fig.7-17: Connection diagram X1
7.5 Switch contact output X2
This function is not available with P30 e-series.
The switch contact output X2 (signal contact) is a floating relay contact and
can be used as a charging status display (default use) or contactor monitor-
ing. The terminal is designed as a spring-type terminal.
The use of the switch contact output must be activated with a DIP switch set-
ting (DSW1.2 to ON).
DSW1.2 OFF means X2 is used as the charge status indicator.
DSW1.2 ON means X2 is used as contactor monitoring.
For further information see 8.1 DIP switch settings.
Charging status display
Switch contact State of the charging station
Open
Charging station not available.
Vehicle is connected, charging station not in
operation or faulty.
Closed
Charging station available.
Charging station is ready for operation and
no vehicle is connected.