EasyManua.ls Logo

Kentec Electronics Sigma A-CP - Default Operation

Kentec Electronics Sigma A-CP
107 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Default Operation
The Sigma A-CP Fire Control Panel must be programmed for default operation prior to configuring.
Default operation includes the programming of default settings and well as the disabling of all
remaining codes. Perform these tasks prior to configuring to ensure proper function of the fire control
panel.
CAUTION!
Programming Default Settings
Program codes 00 and 10 to complete default setting requirements of the Sigma A-CP Fire Control
Panel.
To program default settings of the fire control panel:
1 Turn the Enable Access key to the right to enter Access Level 2.
2 Move the Write Enable slide-switch to the left to enter Access Level 3.
The Write Enable slide-switch is located on the lower-right portion of the fascia adjacent
to the Processor Reset button.
The fire control panel beeps three-times to indicate entry in Access Level 3.
The beeping continues to indicate Access Level 3 operation.
Unintended settings can lead to unintended operation of the fire control panel. Clear the
configuration memory of the fire control panel and program default settings before
programming the new fire control configuration.
www.acornfiresecurity.com
www.acornfiresecurity.com

Table of Contents