The figure below illustrates the Write Enable switch on the fascia of the Sigma A-CP Fire Control
Panel:
Figure 4- 3
Write Enable Slide-Switch
Code 00 is displayed on the menu of the Mode LED after entering Access Level 3.
3 Choose code 00 from the menu and press Enter to set the code.
A flashing dot is displayed in the lower-right-corner of the Mode LED to identify the set code.
The figure below illustrates a code 00 set and code 00 not set in the menu:
Figure 4- 4
Code 00 Set and Code 00 Not Set
Mode
Enable Access
00.
Code Set When
Dot Flashing
Mode
Enable Access
00
Code Set When Not
Dot FlashingNot
A flashing dot is shown in the left
Mode illustration indicating that
the configuration code is set.
A flashing dot is absent from the
right Mode illustration indicating
that the configuration code is not
set.