EasyManua.ls Logo

Kewtech KT63 - Loop Test Range Accuracy; RCD Test Range Accuracy

Kewtech KT63
13 pages
Print Icon
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
kewtechcorp.com
24
RCD Test range accuracy
Supply voltage 195V – 253V AC 50Hz
Test current accuracy (½ I) –0% to –10%
Test current accuracy (I, 5I) +0% to +10%
Trip time accuracy up to 1 second ±(1% + 1ms)
Trip time accuracy over 1 second ±(1% +10ms)
For repair and calibration please return to us at :
Express Cal, Unit 2,
Shaw Wood Business Park, Shaw Wood Way, Doncaster DN2 5TB
Kewtech Corporation Limited
Midas House
Unit 2b, Stones Courtyard,
High Street, Chesham, Bucks HP5 1DE
T: 01494 792 212
F: 01494 791 826
E: sales@kewtechcorp.com
Loop Test Range Accuracy
Range Accuracy
No trip 0.00 – 9.99 Ω ± 5% ± 5 digits
No trip 10.00 – 99.9 Ω ± 3% ± 3 digits
No trip 100 - 500 Ω ± 3% ± 3digits
High Current 0.00 - 500 Ω ± 3% ± 3 digit

Related product manuals