Stratos-Micra INSTALLERS HANDBOOK Iss. 16
10.1 Diagnostics
The remote control software includes a diagnostic function which carries out a number
of checks to verify the correct functioning of the detector. A good time to run these
tests is as a part of planned maintenance. To call up diagnostic mode, select the menu
options “View Diagnostics” or click on the symbol indicated below.
The following message will then appear on the screen:
The software will then scan the loop for up to 127 detectors. For a single detector, wait
until the first detector has been identified and the window indicates that it is scanning
for Detector 2, then press the Cancel button.
The following window appears:
Click on the list entry to highlight it and click on the “Diagnostics…” button. The
software will then commence the system tests. During the “Aspirator and flow” test,
the detector fan will suddenly slow down, but this is a normal part of the test and no
cause for alarm.