Kidde Gemini II System
Figure E-2. RHU Wiring Diagram
RELEASE OF TWO SOLENOIDS
(SEE NOTE 2)
WF
(CLASS B
STYLE B)
(CLASS B
STYLE B)
(CLASS B
STYLE B)
ABORT/SUPV 2
MANUAL
RELEASE
SUPV 1
FROM PREVIOUS DEVICE
CH 1
TO NEXT DEVICE
CH 1
FROM PREVIOUS DEVICE
CH 2
TO NEXT DEVICE
CH 2
RESETTABLE
POWER
NON-RESETTABLE
POWER
24 VDC
BATTERIES
WATER-FLOW CKT.
(CLASS B, STYLE B)
(SEE NOTE 1)
DET. CKT. 2
(CLASS B, STYLE B)
MAX. 40 DETECTORS
(SEE NOTE 1)
DET. CKT. 1
(CLASS B, STYLE B)
MAX. 40 DETECTORS
(SEE NOTE 1)
SIG. CKT. 2
(CLASS B, STYLE Y)
(SEE NOTE 1)
SIG. CKT. 1
(CLASS B, STYLE Y)
(SEE NOTE 1)
(+)
(-)
(+)
(-)
-
+
-
+
_
+
RESET NON-RESET
-
2+R1-R2-
+
R2+ 1-R1+ 2- 2+1-1+ 2- 1+
W108
W109
TB6TB3TB1000
120/240 VAC
50/60 Hz
MAINS SUPPLY
J1
J1001
J1000
TB7 TB5
W101 W104
A1 B2A2B1 A1 B1 A2 B2
+- +-
2-2-1+
+-
2+ 1+1- 2+ 2-1+1- 2+ 1-
OPTIONAL RELAY BOARD WITH 5 FORM C
PROGRAMMABLE RELAYS
TB1
SWITCH SW2 SETTINGS FOR REMOTE HAZARD
UNIT NETWORK ADDRESS
10K
5%
0.5W
EOL
10K
5%
0.5W
EOL
10K
5%
0.5W
EOL
3.9K
5%
0.5W
EOL
3.9K
5%
0.5W
EOL
L
L
LS
S
S
S
L
S
L
S
S
L
L
S
SW2
L
L
S
S
(-)
(+)
(-)
(+)
-
+
BK RD BK RD
7
1
(-)
SD
(+)
(-)
(+)
2
3
6
7
1
(-)
SD
(+)
(-)
(+)
2
3
6
7
1
(-)
SD
(+)
(-)
(+)
2
3
6
7
1
(-)
SD
(+)
(-)
(+)
2
3
6
10K
5%
0.5W
EOL
10K
5%
0.5W
EOL
10K
5%
0.5W
EOL
N
L
AC 120/240
NEUTRAL
CHASSIS
GND.
LINE
S
L
S
L
S
L
S
HIGH VOLTAGES MAY BE PRESENT WHEN
CONNECTING AC POWER TO THE CONTROL PANEL.
TAKE SUITABLE PRECAUTIONS TO AVOID INJURY.
USE 15A BREAKER OR LESS
WARNING
0.5A COMBINED TOTAL
24 VDC
3. FOR LIST OF COMPATIBLE DEVICES, REFER TO APPENDIX B.
4. STOP VALVES ARE REQUIRED FOR SYSTEMS WITH CLUSTERED
CYLINDERS. IF UNUSED, TERMINATE WITH 2K, 5% 1WATT RESISTOR.
SOUNDER2 CIRCUITS ARE SHOWN AS CLASS B STYLE Y,
THESE CAN ALSO BE WIRED AS CLASS A STYLE D AND
DUMMY RESISTOR IS 2K, 5%, 1 WATT.
2. THE VALUE OF THE RELEASE CIRCUIT
1. ALTHOUGH DET1, DET2, AND W-FLOW CIRCUITS ARE
FOR DETAILS.
CLASS A STYLE Z RESPECTIVELY. SEE FIGURE E-1
SHOWN AS CLASS B STYLE B AND SOUNDER1 AND
NOTES:
5. - FOR SUPERVISED CIRCUITS
-
FOR POWER LIMITED CIRCUITS ROUTED
SEPARATELY FROM NON-POWER LIMITED
WIRES BY MORE THAN ¼ INCH. REFER TO FIGURE E-10.
L
S
6.FOR CONFIGURATION OF SHORTING LINKS, REFER TO
FIGURE E-6.
7.FOR DETAILS OF RELEASE CIRCUITS, REFER TO
FIGURE E-7.
8.FOR DETAILS OF RS-485 WIRING, REFER TO FIGURE E-9.
9. FOR CANADIAN APPLICATIONS, ALL FIELD LOCATED EOL
RESISTORS MUST BE MOUNTED IN AN EOL BACKBOX
(P/N 06-129963-001).
SIGNAL
SUPERVISORYPOWER ON
ALARM
UNIT
TROUBLE
SIGNAL
SUP/TBL
SCROLL
REMOTE
HAZARD
ALARM
SCROLL
CONTROLS
SYSTEM
RESET
SILENCE
SILENCED
R
R
STOP VALVE
(SEE NOTE 4)
BK RD
L
S
Switch PositionRHU
Network Address
SW2-1 SW2-2 SW2-3
1 OFF OFF OFF
2ONOFFOFF
3 OFF ON OFF
4ONONOFF
5OFFOFFON
6ONOFFON
7 OFF ON ON
INVALID ONONON