2-9November 2002 06-235975-001
Kidde Gemini II System
OptRyIsoFAIL Optional relay isolation failure.
Prog Rel ISO MCP programmable relay isolated.
PSU FLT Power supply failure .
RegisterFAIL The operator is trying to register a Re-
mote Hazard or Remote Display Unit,
but the registration has failed.
ReleaIsoFAIL Release isolation failure.
Release FLT Fault on agent release output circuit.
Release ISO Agent release output has been iso-
lated.
Release/Sla. MCP has activated its agent release
at the request of a stop valve control
slave.
Releasing Agent release circuit is activated and
releasing agent to the hazard.
Reset RESET button was pressed on the
front panel of one of the units.
Reset by MCP Unit was reset from the Main Control
Panel.
Snd1 LoadFLT Sounder 1 is drawing too much cur-
rent.
Snd1 o/c FLT Sounder 1 is open circuit.
Snd1 s/c FLT Sounder 1 is short circuit.
Snd2 LoadFLT Sounder 2 is drawing too much cur-
rent.
Snd2 o/c FLT Sounder 2 is open circuit.
Snd2 s/c FLT Sounder 2 is short circuit.
Sounder ISO Indicating (sounder) output circuit has
been isolated.
Stp/valvFAIL Failure to update an RHU with its stop
valve control status.
S/valv FLT Stop valve output fault.
Superv FLT Fault on the supervisory input circuit.
Supervisory Supervisory input received.
Suprv IP ISO Supervisory input circuit has been iso-
lated by the operator.
Supv IsoFAIL Supervisory isolation failure.
Switch FLT RDU has detected abort/manual re-
lease switches but is configured not to
have them.
Trbl Rel ISO MCP trouble relay has been isolated
by the operator.
Unregistered The Main Control Panel is communi-
cating with a Remote Hazard Unit, but
the unit is not registered.
Update FAIL The Main Control Panel could not get
an update of events from the Remote
Hazard or Remote Display Unit.
W/F loop FLT Break in waterflow wiring loop on a
Style D circuit.
W/Flo IP ISO Waterflow input has been isolated by
the operator.
W/Flow FLT Fault on the waterflow input circuit.
W/T Abort Abort activated during walk test.
W/T Man.Rel. Manual release activated during walk
test.
W/T Superv. Supervisory activated during walk test.
W/T W/Flow Waterflow input activated during walk
test.
W/T Zone 1 Zone 1 detectors activated during walk
test.
W/T Zone 2 Zone 2 detectors activated during walk
test.
WalkTestFAIL Failure to correctly begin a walk test.
Waterflow Release circuit is activating the sprin-
kler system.
Wflo IsoFAIL Failure to isolate waterflow input on an
RHU.
Zn1 Loop FLT Break in Zone 1 wiring loop on Style D
circuit.
Zn2 Loop FLT Break in Zone 2 wiring loop on a Style
D circuit.
Zone 1 FLT Zone 1 detectors open circuit.
Zone 2 FLT Zone 2 detectors open circuit.