Rate Compensation Heat Detectors
Series 302 heat detectors are designed for use in normal environments as well as environments
where the detectors are subject to weather, moisture (internal condensation), and explosive
atmospheres. They are normally-open devices designed to close an electrical circuit upon
activation. All models feature rate compensation and are available with either 135 °F (57.2 °C)
or 194 °F (90 °C) ratings. They are self restoring, hermetically sealed, shock and corrosion
resistant, and are tamperproof.
Sensor’s Rated
Temperature
Minimum Ambient
Air Temperature
Maximum Ceiling
Temperature
135 °F (57.2 °C) -40 °F (-40 °C) 100 °F (38 °C)
194 °F (90 °C) -40 °F (-40 °C) 150 °F (66 °C)
The sensor's aluminum tube acts as a heat collector when sources of heat radiate directly
on the tube. Install these sensors out of direct sunlight and away from radiating heat sources
including the direct flow from heaters and heat ducts.
302-AW-135 All-weather Heat Detector - Vertical Mounting FM & UL, 135 °F (57.2 °C) Data Sheet K85001-0589
302-AW-194 All-weather Heat Detector - Vertical Mounting FM & UL, 194°F (90 °C) Data Sheet K85001-0589
302-ET-135 All-weather Heat Detector - Vertical, Box Mount (½" NPT), FM & UL, 135 °F (57.2 °C) Data Sheet K85001-0589
302-ET-194 All-weather Heat Detector - Vertical, Box Mount (½" NPT), FM & UL, 194°F (90 °C) Data Sheet K85001-0589
302-EPM-135 Heat Detector - Explosionproof Mounting UL (Not FM approved), 135 °F (57.2 °C) Data Sheet K85001-0589
302-EPM-194 Heat Detector - Explosionproof Mounting UL (not FM approved), 194°F (90 °C) Data Sheet K85001-0589
AP-P Adaptor plate for mounting 302 and 302-AW to any 3" box or 4" octagon outlet box Data Sheet K85001-0589
JALX11 Explosion proof outlet body with cover - Killark Data Sheet K85001-0589
Explosionproof/weatherproof Manual Stations
MPSR Series explosionproof/weatherproof manual pull stations are noncoded re alarm
stations solidly constructed of die-cast material. They are rated for Class I Group B (hy-
drogen) C & D, Class II Groups E. F, G, Class III environments, and are rated NEMA 4X for
outdoor use. Key and screw reset models feature terminal connections and come complete
with backbox.
Hex Screw Reset Cat 45 Key Reset Manual Stations Data Sheet K85001-0588
MPSR1-DHTWX-GE MPSR1-D45WX-GE Explosionproof Single-action, SPST with backbox.
MPSR1-SHTW-GE MPSR1-S45W-GE Weatherproof Single-action, SPST with backbox.
MPSR1-DHTW-GE MPSR1-D45W-GE Weatherproof Single-action, DPDT with backbox.
MPSR2-SHTW-GE MPSR2-S45W-GE Weatherproof Double-action, SPST with backbox.
MPSR2-DHTW-GE MPSR2-D45W-GE Weatherproof Double-action, DPDT with backbox.
MPSR2-SHTW-GE-NYW MPSR2-S45W-GE-NYW Weatherproof Double-action, SPST with backbox, NYC white stripe.
For French markings add -F to the sufx of the model number. For bilinguial French/English markings add -B to the suffix of the model number.
MPSR-LP Double action cover for explosionproof manual stations
MPSRGR10 Replacement glass rods for MPSR stations (10 pack).
276-K1 Cat 45 Key (each)
Initiating Devices