Sirius Capacitor Module – User Manual Model Number - 3550-48-B-1.7C-M-SD-A-G
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. | www.kilowattlabs.com
6
→ Do not dispose the Module in a fire.
→ Do not charge the Module when the temperature is below -30
o
C.
→ Do not charge the Module when temperature is above 80
o
C.
→ Do not operate the Module above the specified voltage.
→ Under no circumstances charge/discharge the Module at more than 125A.
→ Under no circumstance must the charging voltage exceed 55 V
dc
for more than 60 seconds.
→ Do not expose the Module to temperatures in excess of 80°C.
→ Do not place the Module near a heat source, such as a fireplace.
→ Do not disassemble the Module under any circumstances.
→ Do not touch the Module with wet hands.
→ Do not expose the Module to moisture or liquids.
→ Keep the Module away from children and animals.
→ Ensure precautions to prevent short-circuit under all circumstances.
→ Do not connect or disconnect terminals from the Module without first disconnecting the load.
→ Do not touch the terminals with conductors while the Module is charged. Serious burns, shock, or
material fusing may occur.
→ Protect surrounding electrical components from incidental contact.
→ When connecting to external devices ensure that galvanic isolation does not exceed 1000V.
→ Do not use the Module in open-environment, in rain or in a place exposed to water and other
liquids.
→ Do not subject the Module to high pressure.
→ It is not recommended to stack more than 2 Modules.
→ Do not step on the Module.
→ Do not drop the Module. Internal damage may occur that will not be visible.
→ Do not stack Modules once they have been removed from the packaging, instead the Modules
should be placed on shelving.
→ In case the Module is physically damaged due to any event, do not install and energize the Module
under any circumstances and immediately contact your Reseller.
1.3 Modules Connection Safety Precautions:
→ All Modules must be at 100% SOC before connecting in Series or in Parallel.
→ The maximum number of Modules that can be connected in series is 8 with Module Combiner.
→ Do not connect more than 8 Modules in Series.
→ Modules cannot be connected in Series-Parallel combination under any circumstance.