Sirius Capacitor Module User Manual Model Number - 3550-48-B-1.7C-M-SD-A-G
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. | www.kilowattlabs.com
6
Do not dispose the Module in a fire.
Do not charge the Module when the temperature is below -30
o
C.
Do not charge the Module when temperature is above 80
o
C.
Do not operate the Module above the specified voltage.
Under no circumstances charge/discharge the Module at more than 125A.
Under no circumstance must the charging voltage exceed 55 V
dc
for more than 60 seconds.
Do not expose the Module to temperatures in excess of 80°C.
Do not place the Module near a heat source, such as a fireplace.
Do not disassemble the Module under any circumstances.
Do not touch the Module with wet hands.
Do not expose the Module to moisture or liquids.
Keep the Module away from children and animals.
Ensure precautions to prevent short-circuit under all circumstances.
Do not connect or disconnect terminals from the Module without first disconnecting the load.
Do not touch the terminals with conductors while the Module is charged. Serious burns, shock, or
material fusing may occur.
Protect surrounding electrical components from incidental contact.
When connecting to external devices ensure that galvanic isolation does not exceed 1000V.
Do not use the Module in open-environment, in rain or in a place exposed to water and other
liquids.
Do not subject the Module to high pressure.
It is not recommended to stack more than 2 Modules.
Do not step on the Module.
Do not drop the Module. Internal damage may occur that will not be visible.
Do not stack Modules once they have been removed from the packaging, instead the Modules
should be placed on shelving.
In case the Module is physically damaged due to any event, do not install and energize the Module
under any circumstances and immediately contact your Reseller.
1.3 Modules Connection Safety Precautions:
All Modules must be at 100% SOC before connecting in Series or in Parallel.
The maximum number of Modules that can be connected in series is 8 with Module Combiner.
Do not connect more than 8 Modules in Series.
Modules cannot be connected in Series-Parallel combination under any circumstance.