73
73
Chapter 8 Maintenance
Many factors such as ambient temperature, humidity, dust, vibration, internal component aging, wear and
tear will give rise to the occurrence of potential faults. Therefore, it is necessary to conduct routine
maintenance to the drives.
Notes:
As safety precautions, before carrying out check and maintenance of the drive, please ensure that
The drive has been switched off;
The charging LED lamp inside the drive is off.
Use a volt-meter to test the voltage between terminals (+) and (-) and the voltage should be below 36V.
8.1Daily Maintenance
The drive must be operated in the environment specified in the Section 2.1. Besides, some unexpected
accidents may occur during operation. You should maintain the drive conditions according to the table below,
record the operation data, and find out problems in the early stage.
Table 8-1 Daily checking items
Items
Instructions
Criterion
Items
Cycle
Checking methods
Operating
environment
Temperature and
humidity
Any time
Thermometer and
hygrometer
-10℃~+40℃,
derating at 40℃~50℃
Dust and water dripping
Visual inspection
Gas
olfactometry
Drive
Vibration and heating
Any time
Touch the case
Stable vibration and proper
temperature
Noise
Listen
No abnormal sound
Motor
Heating
Any time
Touch by hand
No overheat
Noise
Listen
Low and regular noise
Operating
status
parameters
Output current
Any time
Current meter
Within rated range
Output voltage
Volt-meter
Within rated range
Internal temperature
Thermometer
Temperature rise is less than 35℃
8.2Periodical Maintenance
Customer should check the drive every 3 months or 6 months according to the actual environment.
Notes:
1. Only trained personnel can dismantle the drive to replace or repair components;
2. Don't leave metal parts like screws or pads inside the drive; otherwise the equipment may be damaged.
General Inspection
1. Check whether the screws of control terminals are loose. If so, tighten them with a screwdriver;
2. Check whether the main circuit terminals are properly connected; whether the mains cables are over
heated;
3. Check whether the power cables and control cables are damaged, check especially for any wear on the
cable tube;
4. Check whether the insulating tapes around the cable lugs are stripped;

Table of Contents

Other manuals for Kinco FV20-4T-0037G/0055L

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kinco FV20-4T-0037G/0055L and is the answer not in the manual?

Kinco FV20-4T-0037G/0055L Specifications

General IconGeneral
BrandKinco
ModelFV20-4T-0037G/0055L
CategoryDC Drives
LanguageEnglish

Related product manuals