Chapter 6 List of Parameters
70
code
Name Descriptions Unit
Factory
setting
Modif
Setting
range
b1.08 AVR function 0: Disable
1: Enable all the time
2: Disabled in Dec process
1 2 X 0 2
b1.09 VF Output Voltage
Selection
0: None
1: AI1
2: AI2
3: Keyboard potentiometer
1 0 X 0 3
b1.10 VF Output Voltage
Offset Selection
0: None
1: AI1
2: AI2
3: Keyboard potentiometer
1 0 X 0 3
Group b2.Enhanced parameters
b2.00 Carrier wave frequency 2.0 15.0KHz 0.1 8.0 O 20 150
b2.01 Auto adjusting of CWF 0: Disable
1: Enable
1 1 O 0 1
b2.02 Voltage adjustment
selection
: Over-voltage at
stall Selection
0: Disable
(When install brake resistor)
1: Enable
: Not stop when
instantaneous stop function selection
0: Disable
1: Enable
(Low voltage compensation)
: Over
modulation selection
0: Disable
1: Enable
1 001 X 0 111H
b2.03 Over voltage point atstall 120.0% 150.0%Udce 0.1% 140.0% X 1200
1500
b2.04 Droop control 0.00 10.00Hz 0.00 0.00Hz O 0 1000
b2.05 Auto current limiting
threshold
20.0% 200.0%Ie 0.1% 150.0% X 200 2000
b2.06 Frequency decrease rate
when current limiting
0.00 99.99Hz/s 0.01
Hz/s
1.00Hz/s O 0 9999
b2.07 Auto current limiting
selection
0: Invalid at constant speed
1: Valid at constant speed
Note: It is valid all the time at Acc/Dec
1 1 X 0 1
b2.08 Gain of Slip
compensation
0.0 300.0% 0.1% 100.0% O 0 3000
b2.09 Slip compensation limit 0.0 250.0% 0.1% 200.0% O 0 2500
b2.10 Slip compensation time
constant
0.1 25.0s 0.1s 2.0s O 0 250
b2.11 Auto energy-saving
function
0: Disable
1: Enable
1 0 X 0 1