EasyManua.ls Logo

Kingspan Klargester BioTec+ Control Panel - Gravity Tank; Pumped Outlet Tank; Manual System Check

Kingspan Klargester BioTec+ Control Panel
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1014336 Issue 01 BioTec+ Control Panel User Manual
9
6.4 Gravity Tank
I. Wire the mains into the isolator in the blower housing.
II. Turn the control panel on, it will prompt user to set the RTC (Real Time Clock), which
is the current time. When the RTC is set and you want to change it, simply navigate
from the status screen (the default screen with BioTec+ ) with the arrow keys to the
menu point Set clock”.
6.5 Pumped Outlet Tank
I. Wire the mains into the isolator in the blower housing.
II. Wire the pump and HLA (High Level Alarm) into the control panel.
III. Turn the control panel on, it will prompt user to set the RTC (Real Time Clock), which
is the current time. When the RTC is set and you want to change it, simply navigate
from the status screen (the default screen with BioTec+ ) with the arrow keys to the
menu point Set clock”.
6.6 Manual System Check
The BioTec+ panel allows manual operaon of blower (aeraon and clearwater removal) and submersible
pump. By holding the system check opon for 2 secs, this will only check the valves only.
Using the up/down arrows, select manual operaon of each of the valves and electrical outputs and press ok,
then select each operaon by pressing ok, then ok to switch on to test and ensure its switched back o when
complete.
There, the installer can check:
I. Blower + aeration
II. Blower + Clearwater airlift (Gravity system)
III. Submersible pump (IPS system)
IV. Status / function of the float switch on digital input 1(Level Beep)

Related product manuals