EasyManua.ls Logo

KMC Controls BAC-19 FlexStat Series - Ethernet Network Wiring Considerations; MS;TP Network Wiring Considerations

KMC Controls BAC-19 FlexStat Series
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BAC-19xxxx FlexStat Application Guide 14 AG200824A
Use external junction boxes above the ceiling
or in another convenient location as needed
to make connections that run to the FlexStat’s
junction box.
Using multiple conductor wires for all inputs
(e.g., 8 conductor) and outputs (e.g., 12
conductor) is recommended. Grounds for all
the inputs can be combined on one wire.
Ethernet Network Wiring Considerations
For BAC-19xxxxCE models (only), plug an
Ethernet patch cable into the back of the
FlexStat.
The Ethernet patch cable should be T568B
Category 5 or better and a maximum of 328
feet (100 meters) between devices.
MS/TP Network Wiring Considerations
Use 18 gauge, twisted-pair, shielded cable with
capacitance of no more than 51 picofarads
per foot (167 pf/m) for all network wiring.
Log in and see the EIA-485 Network Wire
Recommendations Technical Bulletin for
recommendations. For principles and good
practices when connecting an MS/TP network,
see Planning BACnet Networks (Application
Note AN0404A).
To maintain critical communications in case of
an open conductor on the network cable, use
redundant wiring routed separately to enhance
reliability.
Connect no more than 128 addressable
BACnet master devices (total) to one MS/
TP network. The devices can be any mix of
controllers or routers. (Up to 127 slave devices
can also be connected.)
Limiting the MS/TP network size to no more
than about 30 controllers will optimize network
performance.
If the network has more than 31 MS/TP
devices or if the cable length exceeds 4,000
feet (1,220 meters), use a KMD-5575 repeater
(on an MS/TP-only network if the baud rate on
the network is no higher than 38.4K baud) or
a faster BAC-5051E router with an Ethernet
network. For each network segment, connect
the shields to a good earth ground at only
one end of the segment; tape back the shield
ground at the other end. Generally, use no more
than four KMD-5575 repeaters per MS/TP
network.
Use a KMD-5567 surge suppressor where a
cable exits the building.
Avoid possible ground loops. See Avoiding and
Troubleshooting Ground Loops Application
Guide.
For troubleshooting wiring, see Wiring Issues
on page 23 and the MS/TP Troubleshooting
Using a Multimeter - Bifurcation video and
downloadable troubleshooting guide.

Table of Contents