BAC-19xxxx FlexStat Application Guide 7 AG200824A
Start learns as days pass the optimal times to
begin and end occupied mode and adjusts the
schedule times accordingly.
• DCV Mode = Select None, Basic, or Standard
DCV mode. See CO2 Sensors and DCV
Operation on page 11.
• AUX Heat = Select None, 3rd stage, or
Compressor Lockout for (HPU) Auxiliary Heat.
Trends and Alarms
NOTE: Trend logs for the space temperature,
active cooling setpoint, and active
heating setpoint are created by default.
Use KMC software to access these
features.
PASSWORDS
FlexStats have security options for two levels of
passwords as described below and in Advanced
(Menu Options) on page 4.
LEVEL DEFAULT PROTECTS DESCRIPTION
Level 1 0000 Setpoints Four digits, with
each digit being a
number 0 to 9. If
all four numbers
are 0, no pass-
word is required
of the user for
that level.
Level 2 (See the
Conquest
Controllers
Default
Password
Technical
Bulletin)
Conguration
NOTE: If an optional Level 1 password is
set, users must enter that password
to change a setpoint. No password
required (0000) is the default.
NOTE: FlexStats are factory-set with a default
Level 2 password for conguration.
For more information about the default
password, log in to the KMC web site
and see the Conquest Controllers
Default Password Technical Bulletin.
NOTE: For security purposes, change the
controller’s default password(s). Be
sure to document any changes made
to passwords!
COMMUNICATION OPTIONS
Conguration via Display Menus
NOTE: FlexStat communications can be set
in the built-in display menu system or
through software.
Use the built-in menus to select the appropriate
MS/TP or Ethernet/IP communication method and
address information. See Communications (Menu
Options) on page 5.
Ethernet/IP Conguration via Software
“E” model FlexStats have a default conguration of
BACnet Ethernet and a Device ID of 1. To cong-
ure the FlexStat to BACnet IP using KMC software
(see the BAC-190000 Series FlexStats data sheet
for versions that support FlexStats), perform the
following steps:
1. If necessary to see the FlexStat under Network
Manager, add or change a port in BACstac to
Ethernet:
A. Click the Microsoft
®
Windows
®
Start Menu
at the lower left corner of the screen.
Starting BACstac
B. Click Cimetrics.
C. Click Congure BACstac.
Creating an Ethernet Port in BACstac
D. Click Add.