BAC-19xxxx FlexStat Application Guide 22 AG200824A
Using KMC software, check the outputs.
Check that the output object (e.g., BO4) is not
congured as Out Of Service.
Check for proper output object conguration.
Check that the output is on.
See Wiring Issues on page 23.
Restart the FlexStat.
Updating Firmware Issues
NOTE: Use KMC software to update rmware
over the network. See the BAC-190000
Series FlexStats data sheet for
versions of KMC software that support
the FlexStat.
Finding and Selection Issues
To view and download rmware updates from
FlexStat product pages on the KMC Controls
web site, you must log in with a valid user
name and password.
Use rmware designated for over-the-
network updates. Firmware meant for the
HTO-1104 Firmware Upgrade Kit will not work
over the network.
Ensure rmware for the correct model is
selected. If rmware for the wrong model
is accidentally installed, the outputs will not
match the applications/conguration on the
display.
NOTE: Backing up the existing settings and
rmware image before or during the
upgrade process is recommended
practice.
Malfunction after Firmware Update
Restart the FlexStat.
Check the application conguration.
NOTE: Restoring to the factory defaults and
reconguring might be needed if how
Damper/Economizer Does Not Work
Enable the economizer in the System section
of Settings.
Connect to the correct output.
Fan Does Not Run
NOTE: The animated fan icon is coupled with
BV1 in the packaged programming (not
the actual fan output terminal).
Select Occupied mode from the Home screen
by pressing the icon.
Override the fan to On from the Home screen
by pressing the icon.
See Wiring Issues on page 23.
Check that the appropriate application is
selected.
Check the fan.
Restart the FlexStat.
Relay (External) Does Not Work
See Analog Output Does Not Work on page
21.
See Relay (Internal) Does Not Work on page
22.
Relay (Internal) Does Not Work
CAUTION
Relays are for Class-2 voltages (24
VAC) only. Do not connect line voltage
to the relays!
NOTE: Max. output current is 1 A for individual
relays @ 24 VAC/VDC or a total of 1.5
A per bank of 3 relays (relays 1–3 and
4–6). Do not attach a device that draws
current that exceeds the corresponding
value. Relays are NO, SPST (Form “A”).
Check the current draw of load. Substitute an
output device that draws less current.