BAC-19xxxx FlexStat Application Guide 5 AG200824A
Schedule (Menu Options)
NOTE: If no schedule is set, the FlexStat will
remain in continuous occupied state as
a default.
Setpoint Hold = Select to run the Schedule or
Hold the current setpoint.
Entire Week = Set a schedule that applies to all
seven days.
Weekdays = Set a schedule that applies to
Monday through Friday (only).
Weekend = Set a schedule that applies to
Saturday and Sunday (only).
Individual Days = Set a schedule that applies
to designated days only.
Holidays = Set a schedule that applies to
designated holidays.
Set Clock (Menu Options)
Date = Set the date for initial or stand-alone
operation.
Time = Set the time for initial or stand-alone
operation.
UTC-Offset = Set the optional UTC offset for
the relevant time zone (see Appendix: UTC
Offset Time Zones on page 25).
DST Enable = Manually turn on/off Daylight
Saving Time mode.
DST Auto = Enable/disable automatic Daylight
Saving Time mode.
Setpoints (Menu Options)
Occupied Cooling = Set the Occupied Cooling
setpoint.
Occupied Heating = Set the Occupied Heating
setpoint.
Unoccupied Cooling = Set the Unoccupied
Cooling setpoint.
take effect. After restarting, most settings will
change back to their defaults.
NOTE: For customizing the display, see
Display Customization on page 9.
Communications (Menu Options)
NOTE: On “E” models, the default protocol is
BACnet over Ethernet with a Device ID
of 1. To see new “E” models in software,
be sure the software attached to the
network can discover BACnet over
Ethernet devices. (Add a BACnet over
Ethernet network in BACstac for KMC
Connect and TotalControl if needed.)
See Ethernet/IP Conguration via
Software on page 7.
Device Instance = Enter the Device Instance.
Baud Rate = Select MS/TP baud rate selection
(9600 to 115200).
MAC Address = Enter the MAC address (on
MS/TP models).
Comm Type = Select IP or Ethernet (on
Ethernet models).
IP Mode = Select Normal or Foreign Device.
IP Address = Enter the IP address.
Gateway Address = Enter the Gateway
address.
Subnet Mask = Enter the Subnet mask.
UDP Port = Enter the FlexStat’s UDP port.
BMDP Port = Enter the UDP Port of the BBMD
to which the FlexStat is registering as a foreign
device.
BBMD Address = Enter the remote BBMD IP
address.
Foreign Time To Live = Enter the Interval (in
seconds) at which the FlexStat (if set as a
foreign device) sends a registration message
to the BBMD with which it is registered.