EasyManua.ls Logo

KMC Controls BAC-19 FlexStat Series - Accessing Settings; Configuration Navigation;Selection; Advanced (Menu Options)

KMC Controls BAC-19 FlexStat Series
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BAC-19xxxx FlexStat Application Guide 4 AG200824A
2. Congure the (BACnet MS/TP or Ethernet)
communications settings. See Communica-
tions (Menu Options) on page 5.
3. Congure the system settings. See System
(Menu Options) on page 6.
4. Congure the setpoints. See Setpoints (Menu
Options) on page 5.
5. Congure the time and screen settings. See
Advanced (Menu Options) on page 4.
6. Congure schedules. See Schedule (Menu
Options) on page 5.
Accessing Settings
1. Push and hold the upper left corner of the
screen (space temperature reading) to start.
2. Enter the password. See Passwords on page
7.
3. Press the desired selection.
4. Press Enter.
Conguration Navigation/Selection
1. Press the desired selection.
2. Adjust the default selection or value (by press-
ing the + or ) as desired.
3. Press Enter to save and move to the next set-
ting.
4. Press Done to return to the previous or home
screen.
NOTE: Available options depend on the
FlexStat model and selected
application.
Advanced (Menu Options)
NOTE: Select the (AHU, HPU, RTU, or FCU)
application and (English or Metric)
units BEFORE changing any other
settings. Changing applications later
will reset most settings back to their
defaults. Use Restore APP or software
to verify or change applications.
Password 1 = Set password Level 1 (for
Active Heating and Cooling Setpoints). See
Passwords on page 7.
Password 2 = Set password Level 2 (for
Settings menu)
Display = Display options:
Color Scheme—Select Blue, Grey, Orange, or
Red.
Contrast—adjust the percentage value.
Brightness—adjust the percentage value
(to the minimum needed for the ambient
lighting). Decreasing the default brightness,
decreases energy consumption and
(depending on lighting conditions) often
increases the attractiveness of the display.
Time Format—display the date (if shown) as
12 Hour (MM/DD/YYYY), 12 Hour (DD/MM/
YYYY), 24 Hour (MM/DD/YYYY), or 24 Hour
(DD/MM/YYYY).
Time Date Options—display at the bottom
of the screen Time and Date, Time Only,
Date Only, or None.
Inactivity Timer—Enter the seconds after
the last press that the display blanking
option activates (0=No Blanking, the
default). See the Blanking Options below.
Blanking Options—Select None (default),
Dim (display dims slightly), Backlight Off
(display becomes entirely black), or Inactivity
Screen (only space temperature is displayed
on a black screen).
Lockout— Select None (default), Icon Bar,
or Icon Bar and Setpoints. If selected, the
items value can be changed only in software
until this setting is changed back to None.
Restore APP = Select the application (AHU,
HPU, RTU, or 2- or 4-pipe FCU, dependent
on model) and (English or Metric) units. The
FlexStat will need to restart for this change to

Table of Contents

Related product manuals