3.11 Generator Storage Procedure
Follow the procedurebelowwhenstoringthegenerator
set for a period of 2 months or more.
Engine Oil
1. Start and run generator set until it reaches
operating temperature or about 15 minutes.
2. Stopgenerator set. Drainoilfromcrankcasewhile
engineisstillwarm. Refillcrankcasewithspecified
weight oil. Replace oil filter.
Gasoline-Fueled Generator Sets
3. Drain the fuel from the fuel tank to prevent
accumulated moisture from mixing with the fuel.
Gaseous-Fueled Generator Sets
With the generator set running, shut off the gas
supply. Operate thegenerator set until theengine
stops from lack of fuel.
Coolant
4. Check the engine coolant protection as described
earlier in the section.
NOTE
Use antifreeze capable of withstanding the lowest
possible temperatures.
Exterior Preparation
5. Clean exterior of generator set and spread a light
film of oil or silicon spray over any exposed
surfaceswhichmaybesubjecttorustorcorrosion.
6. Seal all engine openings with non-absorbent
adhesive tape. Mask off all areas used for
electrical contact.
Battery
7. Disconnect andremove battery. Place battery ina
warm, dry location for storage period. Recharge
once a month to maintain full charge.
Storage
8. Select a well-ventilated (not humid or dusty)
location to store generator.
9. Cover entire unit with a dust cover.